ProtEX PD8-6080/PD8-6081 Explosion-Proof Modbus
®
Scanner Instruction Manual
35
How to Select 5 or 6-Digit Registers
In Master or Snooper Mode, it is possible to select either a five-digit or a six-digit Register Number. Once
the operator has enabled a PV, entered a Slave ID, and chosen a Function Code, the scanner will arrive at the
Register Number menu (
reg.nbr
). Press the Right arrow to display and then the Up arrow to change the
setting for the number of digits used for the Register Number (
5 dig
or
6 dig
), then press ENTER.
Notes:
1. If Function Code 03 is selected, the Register Number defaults to 40001; if Function Code 04 is
selected, the Register Number defaults to 30001.
2. Default Data Type is Float
3. Default Slave ID for PV1=001, for PV2=002, for PV3=003, etc.
The Master ignores the decimal point setting for slave devices that specify a Short or Long integer. For
example, a slave that is displaying 12.34 is read as 1,234. Floating point data may or may not utilize the
decimal point. Refer to the slave’s operating manual to make sure.
The Register Number range is based on the Function Code and the number of digits selected. See the
following table:
Function Code
5 Digit
6 Digit
03
40001
– 49999
400001
– 465536
04
30001
– 39999
300001
– 365536
65
65001-65999
N/A
Slave Mode (
Slave
)
The Slave mode is capable of accepting
Short, Long, and Float data types. Refer to
the Modbus Register Tables at
www.predig.com for details of all the
predefined parameters. Follow the menu
below to navigate and set all parameters
for Slave Mode.
Short
Long
Back To
Forward
to
Byte order is
dependent upon
data type.