ProtEX PD8-6080/PD8-6081 Explosion-Proof Modbus
®
Scanner Instruction Manual
77
Diagnostics Menu (
diag
)
The
Diagnostics
menu is located in the
Advanced
Features
menu, to access
Diagnostics
menu see page
58.
This menu allows the user to test the functionality of all the meter LEDs, check the meter’s software
and version information, and erase the MeterView Pro software installation files from the meter. Press the
Enter
button to view the settings and the Menu button to exit at any time.
Determining Software Version
To determine the software version of a scanner:
1. Go to the
Diagnostics
menu (
diAG
) and press Enter button.
2. Press Up arrow button and scroll to Information menu (
Info
).
3. Press Enter to access the software number (
SFT
) and version (
UER
) information. Write down the
information as it is displayed. Continue pressing Enter until all the information is displayed.
4. The scanner returns to Run Mode after displaying all the settings.
Reset Scanner to Factory Defaults
When the parameters have been changed in a way that is difficult to determine what’s happening, it might
be better to start the setup process from the factory defaults.
Instructions to load factory defaults:
1. Enter the
Advanced
Features
menu, see
page 58.
2. Press Up arrow to go to
Diagnostics
menu
3. Press and hold Right arrow for three seconds, press Enter when display flashes
reset
.
Note: If Enter is not pressed within three seconds, the display returns to Run Mode
.
4. The scanner goes through an initialization sequence (similar as on power-up), and loads the factory
default settings.
Testing the Display LEDs
Enter the Diagnostic menu and press the ENTER button to get to the LED Test menu (
led t
). Press the
ENTER button to activate the LED Test. The PD6080/6081 will cycle through all digits, decimal points, and
relay indicators to enable the operator to see that all are functioning properly. Press the ENTER button
again to access the Information menu (
info
). Press the MENU button to return to Run Mode.
Run Mode
Meter resets
and restarts
with factory
default settings
LED Test:
Cycles through all
digits, decimal pts,
& warning lights.
Press & hold right
arrow for 3 seconds
to reset meter.
Press ENTER while
RESET flashes
to reset meter.
To
RUN Mode
Press & hold MENU Button for 3 seconds
to access the Advanced Features Menu,
then press Up Arrow to scroll through menu
choices until you reach the Diagnostics Menu.