ProtEX PD8-6080/PD8-6081 Explosion-Proof Modbus
®
Scanner Instruction Manual
72
User Menu (
user
)
The
User
menu allows the user to assign the front panel function keys F1, F2, and F3, the digital input F4
(a digital input located on the signal input connector), and up to eight additional digital inputs to access
most of the menus or to activate certain functions immediately (e.g. reset max & min, hold relay states,
etc.). This allows the meter to be greatly customized for use in specialized applications.
Up to eight digital outputs can be assigned to a number of actions and functions executed by the meter
(i.e. alarms, relay acknowledgement, reset max, min, or max & min, tare, and reset tare). The digital
outputs can be used to trigger external alarms or lights to indicate these specific events.
Function Keys & Digital I/O Available Settings
Display
Description
sCan
Scan through all PVs
next
Skip to the next PV
prev
Return to the previous PV
Ack
Acknowledge all active relays that are
in a manual operation mode such as
auto-manual or latching
reset
Directly access the reset menu
Rst Hi
Reset the stored maximum display
values for all channels
Rst Lo
Reset the stored minimum display
values for all channels
Rst HL
Reset the stored maximum & minimum
display values for all channels
relay
Directly access the relay menu
Set 1
*
Directly access the set point menu for
relay 1 (*through 8)
Rly d
Disable all relays until a button
assigned to
enable relays
(
Rly E
) is
pressed
Rly E
Enable all relays to function as they
have been programmed
O Hold
Hold current relay states and analog
output as they are until a button
assigned to
enable relays
(
Rly E
) is
pressed
Display
Description
D Hold
Hold the current display value, relay
states and analog output momentarily
while the function key or digital input is
active. The process value will continue
to be calculated in the background.
disabl
Disable the selected function key or
digital I/O
Contrl
Directly access the control menu
nmenu
Mimic the menu button functionality
(digital inputs only)
Right
Mimic the right arrow/F1 button
functionality (digital inputs only)
up
Mimic the up arrow/F2 button
functionality (digital inputs only)
Enter
Mimic the enter/F3 button functionality
(digital inputs only)
F on 1
*
Force relay 1 (*through 4) into the on
state. This function is used in
conjunction with a digital input to
achieve interlock functionality.
Alrnm 1
*
Provide indication when alarm 1
(*through 8) has been triggered (digital
outputs only)
If installed, there
are up to 8 digital
inputs and outputs.
There are up
to eight Set