Analog Output Source Programming (
aoutpr
)
The 4-20 mA analog outputs can be programmed for source of data, overrange and underrange, absolute
maximum and minimum output, and communications break values. They can also be recalibrated.
•
To calibrate the analog outputs, follow the graphic above.
•
The overrange and underrange values are the values that will be output when the display shows an
overrange or underrange condition. This setting is common to all analog outputs.
•
The maximum and minimum values are the absolute limits for the 4-20 mA output. This setting is
common to all analog outputs.
•
The communications break value determines the mA output when a Slave fails to reply to a command
within the Response time.