ProtEX PD8-6080/PD8-6081 Explosion-Proof Modbus
®
Scanner Instruction Manual
43
The following table shows the system setup for the MTS M-Series gauge, one PD6080 Master, and one
PD6080 Snooper:
Parameter
PD6080
Master
PD6080
Snooper
Descriptio
n/Commen
t
Mode
Master
Snooper
PV1
Slave ID
1
1
Function
Code
04
04
Register
PV1
30001
30001
Tank 1
Product
Level
Data
Type
Long
integer
Binary,
Signed
Long
Byte
Order
1234
1234
PV2
Slave ID
1
1
Function
Code
04
04
Register
PV2
30003
30003
Tank 1
Interface
Data
Type
Long
integer
Binary,
Signed
Long
Byte
Order
1234
1234
PV3
Slave ID
1
1
Function
Code
04
04
Register
PV3
30017
30017
Tank 1
Average
Temperature
Data
Type
Long
integer
Binary,
Signed
Long
Byte
Order
1234
1234
PV4
Slave ID
2
2
Function
Code
04
04
Register
PV4
30001
30001
Tank 2
Product
Level
Parameter
PD6080
Master
PD6080
Snooper
Descriptio
n/Commen
t
Data
Type
Long
integer
Binary,
Signed
Long
Byte
Order
1234
1234
PV5
Slave ID
2
2
Function
Code
04
04
Register
PV5
30003
30003
Tank 2
Interface
Data
Type
Long
integer
Binary,
Signed
Long
Byte
Order
1234
1234
PV6
Slave ID
2
2
Function
Code
04
04
Register
PV6
30017
30017
Tank 2
Average
Temperature
Data
Type
Long
integer
Binary,
Signed
Long
Byte
Order
1234
1234
PV7
Slave ID
3
3
Function
Code
04
04
Register
PV7
30001
30001
Tank 3
Product
Level
Data
Type
Long
integer
Binary,
Signed
Long
Byte
Order
1234
1234
PV8
Slave ID
3
3
Function
Code
04
04