PD2-6300
Helios Large Display Pulse Input Rate/Totalizer Instruction Manual
7
Total Display
& Total
Overflow
0 to 999,999; automatic lead zero
blanking. “T” LED is illuminated while
displaying total or grand total.
Up to 999,999,999 with total-overflow
feature. “
oF
” is displayed to the left of
total overflow and ▲ LED is
illuminated.
Alternating
Display
Either display may be programmed
to alternate between rate and total or
rate and grand total every 10
seconds.
Total Decimal
Point
Up to five decimal places or none:
d
.
ddddd
,
d
.
dddd
,
d
.
ddd
,
d
.
dd
,
d
.
d
, or
dddddd
Total decimal point is independent of
rate decimal point.
Totalizer
Calculates total based on rate and
field programmable multiplier to
display total in engineering units.
Time base must be selected
according to the time units in which
the rate is displayed.
Totalizer
Rollover
Totalizer rolls over when display
exceeds 999,999,999. Relay status
reflects display.
Total Overflow
Override
Program total reset for automatic
with 0.1 second delay and set point 1
for 999,999
Totalizer
Presets
Up to eight, user selectable under
setup menu. Any set point can be
assigned to total and may be
programmed anywhere in the range
of the meter for total alarm indication.
Programmable
Delay
On Release
0.1 and 999.9 seconds; applied to
the first relay assigned to total or
grand total.
If the meter is programmed to reset
total to zero automatically when the
preset is reached, then a delay will
occur before the total is reset.
Total Reset
Via front panel button, external
contact closure on digital inputs,
automatically via user selectable
preset value and time delay, or
through serial communications.
Total Reset
Password
Total and grand total passwords may
be entered to prevent resetting the
total or grand total from the front
panel.
Non-
Resettable
Total
The grand total can be programmed
as a non-resettable total by entering
the password “050873”.
Caution!
Once the Grand Total has
been programmed as
“non-resettable” the
feature
cannot
be
disabled.
Relays
Rating
2 or 4 SPDT (Form C) internal and/or
4 SPST (Form A) external; rated 3 A
@ 30 VDC and 125/250 VAC
resistive load; 1/14 HP (
≈
50 W) @
125/250 VAC for inductive loads
Noise
Suppression
Noise suppression is recommended
for each relay contact switching
inductive loads; see page 16 for
details.
Deadband
0-100% of span, user programmable
High Or Low
Alarm
User may program any alarm for high
or low trip point.
Unused alarm LEDs and relays may
be disabled (turn off).
Relay
Operation
Automatic (non-latching) and/or
manual reset
Latching (requires manual
acknowledge) with/without clear
Pump alternation control (2 to 4
relays)
Sampling (based on time)
Off (disable unused relays and
enable Interlock feature)
Manual on/off control mode
Relay Reset
User selectable via front panel
buttons or digital inputs
1. Automatic reset only (non-
latching), when the input passes
the reset point.
2. Aut manual reset at any
time (non-latching)
3. Manual reset only, at any time
(latching)
4. Manual reset only after alarm
condition has cleared (latching)
Note: Front panel button or digital
input may be assigned to
acknowledge relays
programmed for manual reset.
Time Delay
0 to 999.9 seconds, on & off relay
time delays.
Programmable and independent for
each relay
Fail-Safe
Operation
Programmable and independent for
each relay.
Note: Relay coil is energized in non-
alarm condition. In case of
power failure, relay will go to
alarm state.
Auto
Initialization
When power is applied to the meter,
relays will reflect the state of the
input to the meter.
Isolated 4-20 mA Transmitter Output
Output Source
Process variable (PV), max, min, set
points 1-4, Modbus input, or manual
control mode
Scaling Range
1.000 to 23.000 mA for any display
range
Calibration
Factory calibrated: 4.000 to 20.000 =
4-20 mA output
Analog Out
Programming
23.000 mA maximum for all
parameters:
Overrange, underrange, max, min,
and break
!
www.
.com
1.800.561.8187