PD2-6300
Helios Large Display Pulse Input Rate/Totalizer Instruction Manual
31
Scaling the Meter (
SCALE
)
The process inputs (4-20 mA and
10 VDC) can be scaled to display the process variable in engineering
units. A signal source is not needed to scale the meter; simply program the inputs and corresponding
display values.
For instructions on how to program numeric
Error Message (
Error
)
An error message indicates that the calibration or scaling process was not successful.
After the error message is displayed, the meter reverts to the input prior to the failure during calibration or
scaling and to input 1 during internal calibration, allowing the appropriate input signal to be applied or
programmed.
The error message might be caused by any of the following conditions:
1. Input signal is not connected to the proper terminals or it is connected backwards.
2. Wrong signal selection in
Setup
menu.
3. Minimum input span requirements not maintained.
4. Input 1 signal inadvertently applied to calibrate input 2.
Minimum Input Span
The minimum input span is the minimum difference between input 1 and input 2 signals required to
complete the calibration or scaling of the meter.
Input Range
Input 1 & Input 2 Span
4-20 mA
0.15 mA
10 VDC
0.01 VDC