Helios Large Display Pulse Input Rate/Totalizer Instruction Manual
PD2-6300
6
Isolation
4 kV input/output-to-power line
500 V input-to-output or output-to-P+
supply
Overvoltage
Category
Installation Overvoltage Category II:
Local level with smaller transient
overvoltages than Installation
Overvoltage Category III.
Environmental
Operating temperature range: -40 to
150°F (-40 to 65°C)
Storage temperature range: -40 to
185°F (-40 to 85°C)
Relative humidity: 0 to 90% non-
condensing
Connections
Removable and integrated screw
terminal blocks accept 12 to 22 AWG
wire...
Enclosure
UL Type 4X, IP65 rated.
Polycarbonate & glass blended
plastic case, color: gray. Includes
four PG11 through-hole conduit
openings, with two factory installed
PG11, IP68, black nylon threaded
hole plugs with backing nuts.
Mounting
Wall Mounting:
Four (4) mounting
holes provided for screwing meter
into wall. See Wall Mounting
Instructions on page 11 for additional
details.
Pipe Mounting:
Optional pipe
mounting kit (PDA6260) allows for
pipe mounting. Sold separately. See
Pipe Mounting Instructions on page
12 for additional details.
Tightening
Torque
Removable Screw Terminals:
5 lb-
in (0.56 Nm)
Digital I/O and RS485 Terminals:
2.2 lb-in (0.25 Nm)
Overall
Dimensions
10.63" x 12.59" x 4.77" (270 mm x
319.7 mm x 121.2 mm) (W x H x D)
Weight
6.10 lbs (2.76 kg)
Warranty
3 years parts & labor
Rate Input
Inputs
Field selectable: Pulse or square
wave 0-5 V, 0-12 V, or 0-24 V @ 30
kHz; TTL; open collector 4.7 k
pull-
up to 5 V @ 30 kHz; NPN or PNP
transistor, switch contact 4.7 k
pull-
up to 5 V @ 40 Hz; Modbus PV
(Slave)
Low Voltage
Mag Pickup
(Isolated)
Sensitivity: 40 mVp-p to 8Vp-p
Minimum
Input
Frequency
0.001 Hz
Minimum frequency is dependent on
high gate setting.
Maximum
Input
Frequency
30,000 Hz (10,000 for low voltage
mag pickup)
Input
Impedance
Pulse input: Greater than 300 k
@
1 kHz.
Open collector/switch input: 4.7 k
pull-up to 5 V.
Accuracy
±0.03% of calibrated span ±1 count
Temperature
Drift
Rate display is not affected by
changes in temperature.
Multi-Point
Linearization
2 to 32 points
Low-Flow
Cutoff
0-999999 (0 disables cutoff function)
Decimal Point
Up to five decimal places or none:
d
.
ddddd
,
d
.
dddd
,
d
.
ddd
,
d
.
dd
,
d
.
d
, or
dddddd
Calibration
May be calibrated using K-factor,
internal calibration, or by applying an
external calibration signal.
K-Factor
Field programmable K-factor
converts input pulses to rate in
engineering units. May be
programmed from 0.00001 to
999,999 pulses/unit.
Calibration
Range
Input 1 signal may be set anywhere
in the range of the meter; input 2
signal may be set anywhere above or
below input 1 setting.
Minimum input span between any
two inputs is 10 Hz.
An error message will appear if the
input 1 and input 2 signals are too
close together.
Filter
Programmable contact de-bounce
filter: 40 to 999 Hz maximum input
frequency allowed with low speed
filter.
Time Base
Second, minute, hour, or day
Gate
Low gate: 0.1-99.9 seconds
High gate: 2.0-999.9 seconds
F4 Digital
Input Contacts
3.3 VDC on contact. Connect
normally open contacts across F4 to
COM.
F4 Digital
Input
Logic Levels
Logic High: 3 to 5 VDC
Logic Low: 0 to 1.25 VDC
Rate/Totalizer
Display
Assignment
The Upper and Lower displays may
be assigned to rate, total, grand total,
alternate rate/total, alternate
rate/grand total, set points, alternate
rate/units, alternate total/units,
alternate grand total/units, display Hi,
display Lo, display Hi/Lo, display
modbus, display units (lower display)
and display Off (lower display).
Rate Display
Indication
-99999 to 999999, lead zero
blanking. “R” LED illuminates while
displaying rate.