Pag. 14
4.1. Example of installation with management of alarm events
An installation complete with alarm management includes:
•
2 readers, one in and one out;
•
2 push-buttons for manual door opening;
•
1 electric lock for commanding door opening;
•
1 break-in control opening contact;
•
1 buzzer or other alarm device for signalling break-in.
Connect the input reader 1 to terminals D0.1, D1.1, GND, and +9V of the control unit.
Connect the output reader 2 to terminals D0.2, D1.2, GND, and +9V of the control unit.
Connect the manual door opening push-button 1 between terminals IN1 and +9V of the control unit.
Connect the manual door opening push-button 2 between terminals IN2 and +9V of the control unit.
Connect door electric lock to terminals NO1 and COM1.
Connect opening contact to terminals IN5, de9V of the control unit.
Connect the buzzer to terminals NO5 and COM5.
Configure reader 1 for relay 1 tripping with break-in input IN5.
Configure reader 2 for relay 1 tripping with break-in input IN5.
Configure input IN1 for relay 1 tripping.
Configure input IN2 for relay 1 tripping.
Configure input IN5 for relay 5 tripping.
Set relay 1 tripping and delay times at 5 and 0 seconds, respectively.
Set relay 5 tripping and delay times at 10 and 20 seconds, respectively.
Programme a badge for default access enable (5 Control Unit programming and testing, pag. 16)
After badge clearance the electric lock is tripped and the door released. The door must open within 5 seconds,
after which it must close again within 20 seconds. Failing the foregoing, an ATL event is generated (door open
too long) and the buzzer sounds for 10 seconds.