9410QA01
LERBAKKEN 10, 8410 RØNDE DENMARK
Revision date:
2008-06-10
Version Revision
V2 R1
Prepared by:
PB
Page:
1/3
ATEX Installation drawing
9410
For safe installation of 9410 the following must be observed. The module shall only be
Installed by qualified personnel who are familiar with the national and international laws,
directives and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
9410 Power Control Unit
ATEX Certificate
KEMA 07ATEX0152 X
Marking:
3G Ex nA nC IIC/IIB/IIA T4
Standard:
EN60079-0:2006,
EN60079-15:2005
34
33
32
31
14
13
12
11
9410
91 92 93 94 95
Power
Rail
Supply -
Backup -
COM
NC
NO
Status
24 V
GND
Non Hazardous Area or Zone 2
T4: -20 ºC <Ta < +60ºC
Terminal 34-33
Backup: 21,6 VDC – 26,6VDC / 4ADC
Terminal 31-32
Supply: 21,6 VDC – 26,6VDC / 4ADC
Terminal 11, 12, 13
Power Rail Status Relay
Unclassified installation
250VAC, 2A, 500VA / 30VDC, 2A, 60W
Zone 2 installation:
32VAC, 2A, 64VA / 30VDC, 2A, 60W