9410QF01
LERBAKKEN 10, 8410 RØNDE DENMARK
Revision date:
2009-03-30
Version Revision
V2 R3
Prepared by:
PB
Page:
1/3
FM Installation drawing
9410 Power Control Unit
For safe installation of 9410 the following must be observed. The module shall only be
Installed by qualified personnel who are familiar with the national and international laws,
directives and standards that apply to this area.
c-FM–us Certificate 3034431
Marking
NI, Class I, Division 2, Group A,B,C,D T4 or
Class I, Zone2, AEx nA nC IIC T4
Class I, Zone2, Ex nA nC IIC T4
Standard:
Class 3600,Class 3611, Class 3810, ANSI/ISA 12.00.01 / 12.12.02
ISA 60079-15:2002, CSA-E79-15, CSA-C22.2-213
34
33
32
31
14
13
12
11
9410
91 92 93 94 95
Power
Rail
Supply -
Backup -
COM
NC
NO
Status
24 V
GND
Non Hazardous Area or Division 2 / Zone 2
T4: -20 ºC <Ta < +60ºC
Terminal 34-33
Backup: 21,6 VDC – 26,6VDC / 4ADC
Terminal 31-32
Supply: 21,6 VDC – 26,6VDC / 4ADC
Terminal 11, 12, 13
Power Rail Status Relay
Unclassified installation
250VAC, 2A, 500VA / 30VDC, 2A, 60W
Zone 2 installation:
32VAC, 2A, 64VA / 30VDC, 2A, 60W