User Manual
ScanLog 96 Pen Drive Version
24
RECORDER CONFIGURATION
Table : 10.1
Parameter Description
Settings
(Default Value)
NORMAL INTERVAL
The ScanLog respects this parameter value for generating
periodic records when none of the channels is under Alarm. For
e.g., If this parameter value is set to 0:00:30, then a new record is
generated every 30 Second if no channel is in Alarm.
Setting this parameter value to 0:00:00 disables normal recording.
0:00:00 (H:MM:SS)
to
2:30:00 (H:MM:SS)
(Default : 0:00:30)
The ScanLog respects this parameter value for generating
periodic records when any one or more channels are under Alarm.
For e.g., If this parameter value is set to 0:00:10, then a new
record is generated every 10 Second whenever there is any
channel(s) is in Alarm.
Setting this parameter value to 0:00:00 disables zoom recording.
ZOOM INTERVAL
0:00:00 (H:MM:SS)
to
2:30:00 (H:MM:SS)
(Default : 0:00:10)
Set to ‘Enable’ if a record is to be generated every time the Alarm
status for any of the channels is toggled (On-to-Off or Off-to-On).
ALRM TOGGL REC
Disable
Enable
(Default : Enable)
Continuous
The ScanLog keeps generating records indefinitely. There are no
Start / Stop commands. Suitable for continuous processes.
Batch
The ScanLog generates records over a preset time interval. The
recording begins upon issuance of Start command and continues
until the user set time interval is elapsed. Suitable for batch
processes.
RECORDING MODE
Continuous
Batch
(Default : Continuous)
BATCH TIME
(Available for Batch Recording Mode)
Sets the time period in Hours:Minutes for which the recording to
take place from the time the Start command is issued.
0:01 (HH:MM)
to
250:00 (HHH:MM)
(Default : 1:00)
Section 10
BATCH START
BATCH STOP
These two parameters are also available on Operator parameter
list. Refer Section 4 : Operator Parameters.
No
Yes