 User Manual

ScanLog 96 Pen Drive Version

18

The Channel configuration parameters are listed in Table below and are generally required to be set only at the time of 
installation.

CHANNEL CONFIGURATION

Table : 8.1

Parameter Description

1 or 2

Set the type of Thermocouple / RTD / DC Linear signal input type 
connected to the selected channel.

INPUT TYPE

Refer Table 8.2

(Default : 0 to 10 V)

RESOLUTION

Set the process value indication resolution (decimal point). All the 
resolution  based  parameters  (Hysteresis, Alarm  Setpoints  etc.) 
then follow this resolution setting.

(Applicable only for DC Linear Inputs)

The  transmitter  output  signal  value  corresponding  to  RANGE 
LOW process value. 

Refer 

Appendix-A : DC Linear Signal Interface

 for details.

SIGNAL LOW

Settings 

(Default Value)

Section 8

Input Type

Settings

Default

0 to 20 mA

0.00 to Signal High

0.00

4 to 20 mA

0 to 80 mV

0 to 1.25 V

0 to 5 V

0 to 10 V

1 to 5 V

4.00 to Signal High

0.00 to Signal High

0.000 to Signal High

0.000 to Signal High

0.00 to Signal High

1.000 to Signal High

4.00

0.00

0.000

0.000

0.00

1.000

SELECT CHANNEL

(

This parameter is available for Dual Channel Version only

Select the channel for which parameter settings are desired.

(Applicable only for DC Linear Inputs)

The  transmitter  output  signal  value  corresponding  to  RANGE 
HIGH process value. 

Refer 

Appendix-A : DC Linear Signal Interface

 for details.

SIGNAL HIGH

Input Type

Settings

Default

0 to 20 mA

4 to 20 mA

0 to 80 mV

0 to 1.25 V

0 to 5 V

0 to 10 V

1 to 5 V

Signal Low to 20.00 

20.00

20.00

80.00

1.250

5.000

10.00

5.000

Signal Low to 20.00 

Signal Low to 80.00 

Signal Low to 1.250 

Signal Low to 5.000 

Signal Low to 10.00 

Signal Low to 5.000 

Refer Table 8.2

Select the Units that shall be displayed along with the measured 
PV on the display. For temperature input (Thermocouple & RTD), 
only °C and °F units are available and represent actual converted 
values. All other units available for DC Linear signal input are for 
indication purpose only and should be selected as per the units 
specified by the transmitter. 

UNITS

Refer Table  .3

8

(Default : °C)

Содержание ScanLog 96

Страница 1: ...User Manual ScanLog 96 Pen Drive Version Single Dual Channels Universal Process Data Logger with USB Port for Data Transfer to PC via Pen Drive User Manual ScanLog 96 Pen Drive Version...

Страница 2: ...TION 6 4 OPERATOR PARAMETERS 12 5 ALARMS PARAMETERS 14 6 SUPERVISORYPARAMETERS 16 7 DEVICE CONFIGURATION 17 8 CHANNELCONFIGURATION 18 9 ALARMS CONFIGURATION 23 10 RECORDER CONFIGURATION 24 11 RTC SETT...

Страница 3: ...followed by Units Refer Figure 1 2 a below Boiler Pressure 2 1 PSI INPUT TYPE Type K Cr Al Figure 1 2 a Figure 1 2 b In Set up Mode the Upper Row displays the parameter Name and the Lower Row display...

Страница 4: ...ded for Pen Drive operation ENTER Alarm ACK Symbol Key Function DOWN UP SET UP Press to enter exit Set up Mode Press to decrease the parameter value Pressing once decreases the value by one count hold...

Страница 5: ...ove Max Range Process Value below Min Range Error Message Cause Thermocouple RTD broken Sensor Open Under Range Over Range In case of Dual Channel the channel wise process value indication update depe...

Страница 6: ...2 36 Information Sample Screen NEW RECORDS IN MEMORY Shows the numbers of new records available in the recorder memory for copying downloading to Pen Drive using Copy New command New Records 12523 OLD...

Страница 7: ...cording of the latest available new record in the memory This information does not appear if there are no new records in the memory Last Record Time 14 12 10 RTC Screen This screen provides the Real T...

Страница 8: ...Furnace Test Chamber etc or the location like Paint Room Test Lab etc where recording is performed The Instrument Name is mentioned in the File Header described later section of the file where the sto...

Страница 9: ...is the unique 5 Digit Code just described above For example if the UNIQUE ID NUMBER is 15030006 then the file is named REC30006 csv The records are downloaded to the file on Pen Drive in Comma Separa...

Страница 10: ...he 5 Digit Code and S is the sequential number 1 to 250 assigned to the back up file For example if the 5 Digit Code is 30006 and there does not exist any previous back up file then the new back up fi...

Страница 11: ...ng Upon inserting the Pen Drive into the USB port the ScanLog responds by displaying the message shown in the figure 3 3 a During this time the ScanLog checks the file format on the Pen Drive and also...

Страница 12: ...ion downloads the records that are not yet downloaded even once that is new records After successfully downloading the new records the ScanLog retains this set of records as old records until next suc...

Страница 13: ...reading the user defined Instrument Name File Name Channel Names refer section File System for Read Operation If there is an error in opening the file or any other errors encountered while reading th...

Страница 14: ...when a Pen Drive is attached to the USB socket This list is also presented automatically in the Run Mode upon detection of the Pen Drive insertion Refer Section 3 PEN DRIVE OPERATION for details on e...

Страница 15: ...o start recording the data This is usually issued at the begin of a batch process Available if Batch Recording is selected This parameter is presented only if the batch is already started Through the...

Страница 16: ...larm number or Press UP DOWN Keys to select next Page Press ENTER Key To open Alarm Settings List or Press UP DOWN Keys to select Alarm Number Desired Alarm Number Press ENTER Key to open AL2 Paramete...

Страница 17: ...value ALx TYPE x 1 2 3 or 4 depending upon the Alarm selected AL1 AL2 AL3 orAL4 Setpoint Value for Process High or Process Low Alarm ALx SETPOINT x 1 2 3 or 4 depending upon the Alarm selected AL1 AL...

Страница 18: ...tes how to access the parameters under the supervisory Page Header Alarm Configuration The parameters covered under each Page Header are described in detail in the following sections SUPERVISORY CONFI...

Страница 19: ...command to Yes erases all the records stored in the internal Memory Default No No Yes Settings Default Value Section 7 This parameter value sets the time interval for which each channel is displayed I...

Страница 20: ...gnal High 0 000 to Signal High 0 000 to Signal High 0 00 to Signal High 1 000 to Signal High 4 00 0 00 0 000 0 000 0 00 1 000 SELECT CHANNEL This parameter is available for Dual Channel Version only S...

Страница 21: ...to 30000 Default 0 RANGE LOW Applicable only for DC Linear Inputs The Process Value corresponding to the SIGNALLOW value from the transmitter ReferAppendix A DC Linear Signal Interface for details 30...

Страница 22: ...0 C 328 to 1112 F or 199 9 to 600 0 C 328 0 to 1112 0 F 1 Unit 0 1 Unit 0 01 Unit 0 001 Unit 1 C F or 0 1 C F 1 C or 0 1 C Reserved for customer specific Thermocouple type not listed above The type sh...

Страница 23: ...Torr litre hr litre min RH 2 O Degree Centigrade Degree Fahrenheit No Unit Blank Degree Kelvin Engineering Units Percentage Pascals Mpascals Kpascals Bar Milli bar PSI mm water gauge Inches water gau...

Страница 24: ...on 22 Option Description Milli Amps Milli Volts Ohms Parts per million Revolutions per minute Milli seconds Seconds Minutes Hours PH PH Miles per hour Milli grams Grams Kilo grams mA mV ohm ppm rpm mS...

Страница 25: ...is parameter allows selecting the exact number of Alarms required per channel ALARMS CHAN 1 to 4 Default 4 Section 9 Normal Reverse Default Normal RELAY 1 LOGIC Relay 1 is common forAlarm 1 Alarm 3 fo...

Страница 26: ...sables zoom recording ZOOM INTERVAL 0 00 00 H MM SS to 2 30 00 H MM SS Default 0 00 10 Set to Enable if a record is to be generated every time the Alarm status for any of the channels is toggled On to...

Страница 27: ...Set current calendar month 1 to 12 Set current calendar year YEAR 2000 to 2099 Section 11 UNIQUE ID NUMBER This is a Read only parameter The value shown is arbitrary and will differ from device to dev...

Страница 28: ...n locked condition the instrument asks for UNLOCK Yes No Set the parameter to Yes and the instrument returns to Main Mode Access this parameter again to set the value for UNLOCK to Yes The instrument...

Страница 29: ...l cables 4 Use appropriate fuses and switches wherever necessary for driving the high voltage loads to protect the recorder from any possible damage due to high voltage surges of extended duration or...

Страница 30: ...0 21 23 24 25 26 27 28 Analog Input 1 Analog Input 2 16 17 18 19 20 21 23 24 25 26 27 28 Analog Input 1 Analog Input 2 RTD DC Linear V Use a shielded twisted pair with the shield grounded at the signa...

Страница 31: ...ustrate a few connection examples for channel 1 2 wire Current Transmitter 24VDC Supply 19 18 17 16 15 24V mA 4 to 20mA Output 3 wire Voltage Transmitter 5VDC Supply Supply 1 to 3 6 V Output 21 20 19...

Страница 32: ...mitter signal range fits e g 4 20 mA 2 Signal Low Signal value corresponding to Range Low process value e g 4 00 mA 3 Signal High Signal value corresponding to Range High process value e g 20 00 mA 4...

Страница 33: ...00 mA PV Resolution 0 1 Range Low 50 0 Range High 250 0 X mA Y psi 4 00 20 00 Signal Low Signal High 0 00 Range Low 5 00 Range High Presume the pressure is to be measured with 0 01 Resolution that is...

Страница 34: ...range from the example transmitter is 4 mA 0 0 LPM to 16 mA 75 0 LPM only If no Clipping is applied on the measured flow rate then the scaled PV will also include out of range values for the signal va...

Страница 35: ...w w w p p i i n d i a n e t Process Precision Instruments 101 Diamond Industrial Estate Navghar Vasai Road E Dist Palghar 401 210 Maharashtra India 0250 2391722 33 37 42 07498799226 09321985369 suppo...

Отзывы: