Chapter 5 Function parameter
42
Ch
ap
ter 5
266
F8.11
Fault DO action
selection during
automatic fault reset
0: OFF
1: ON
0
☆
267
F8.12
Automatic fault reset
interval
0.1s to 100.0s
1.0s
☆
268
F8.13
Over-speed detection
value
0.0 to 50.0% (maximum frequency)
20.0%
☆
269
F8.14
Over-speed detection
time
0.0 to 60.0s
1.0s
☆
270
F8.15
Detection value for
too large speed
deviation
0.0 to 50.0% (maximum frequency)
20.0%
☆
271
F8.16
Detection time for too
large speed deviation
0.0 to 60.0s
5.0s
☆
272
F8.17
Fault protection
action selection 1
Units digit: Motor overload (Err.11)
0: Free stop
1: Stop at the selected mode
2: Continue to run
Tens digit: input phase loss (Err.12) (same
as units digit)
Hundred digit: output phase loss (Err.13)
(same as units digit)
Thousand digit: external fault (Err.15)
(same as units digit)
Ten thousands digit: Communication
abnormal( Err.16)(same as units digit)
00000
☆
273
F8.18
Fault protection
action selection 2
Units digit: Encoder fault(Err.20)
0: Free stop
1:Switch to V/F and then stop at the
selected mode
2:Switch to V/F and continue to run
Tens digit: function code read and write
abnormal (Err.21)
0: Free stop
1: Stop at the selected mode
Hundreds digit: Reserved
Thousands digit: Motor overheating
(Err.45) ( same as F8.17 units digit)
Ten thousands digit: Running time
arrival(Err.26)(same as F8.17 units digit)
00000
☆
274
F8.19
Fault protection
action selection 3
Units digit:User-defined fault 1(Err.27)
(same as F8.17 units digit)
Tens digit:User-defined fault 2(Err.28)
(same as F8.17 units digit)
Hundreds digit: Power-on time arrival
(Err.29) ( same as F8.17 units digit)
Thousands digit: Reserve
Ten thousands digit: PID feedback loss
when running (Err.31) (same as F8.17
units digit)
00000
☆