Chapter 5 Function parameter
86
Ch
ap
ter 5
F7.13 Deceleration time 4
0.0s to 6500.0s
-
☆
PI500-E provides 4 groups of deceleration time, respectively F0.13\F0.14 and the above 3
groups of deceleration time.
The 4 groups of deceleration time are defined exactly the same, please refer to the
instructions of F0.13 and F0.14. The 4 groups of deceleration time can be switched through
different combinations of the multi-function digital input terminal DI, please refer to the
instructions of function code F1.00 to F1.07 in the attachment 2 for the detailed application
methods .
F7.14
Switching frequency point between
acceleration time 1 and acceleration time 2
0.00Hz~F0.19(maxim
um frequency)
0.00Hz
☆
F7.15
Switching frequency point between
deceleration time 1 and deceleration time 2
0.00Hz~F0.19(maxim
um frequency)
0.00Hz
☆
The function is active when motor 1 is selected and DI terminal is not selected to switch
between ac/deceleration. It is used to automatically select ac/deceleration time by not DI terminal
but the operating frequency range when the inverter is running.
Output Frequency
(
Hz
)
Set frequency
(
Hz
)
F7.15
F7.14
Acceleration
time 2
Deceleration
time 1
Time(t)
Acceleration
time 1
Deceleration
time 2
Figure5-16:Schematic diagram of switching between acceleration and deceleration
If the operating frequency is less than F7.14, select acceleration time 2; otherwise select
acceleration time 1.
For the above figure in the process of deceleration, if the operating frequency is more than
F7.15, select deceleration time 1; otherwise select deceleration time 2.
F7.16 Forward/reverse rotation dead-band
0.00s~3600.0s
0.0s
☆
It is the waiting time that the inverter reaches zero speed when the parameter is used to switch
between forward and reverse rotation.
Output frequency
Hz
Time(
t)
Forward
Deadband
Reverse
Figure5-17:Schematic diagram of the dead-band of forward and reverse
F7.17 Reverse rotation control
Allow
0
0
☆
Prohibit
1
For certain production equipment, the reverse rotation may result in damage to the
equipment, the function can disable the reverse rotation. The factory default allows reverse
rotation.