Chapter 5 Function parameter
41
Ch
ap
ter 5
247
F7.44
Timing run time
0.0Min to 6500.0Min
0.0Min
★
248
F7.45
Current running
reaches the set time.
0.0Min to 6500.0Min
0.0Min
★
249
F7.46
Awakens frequency
dormancy frequency
(
F7.48
)
to maximum
frequency (F0.19)
0.00Hz
☆
250
F7.47
Awakens delay
time
0.0s to 6500.0s
0.0s
☆
251
F7.48
Dormancy
frequency
0.00Hz to awakens frequency(F7.46)
0.00Hz
☆
252
F7.49
Dormancy delay
time
0.0s to 6500.0s
0.0s
☆
253
F7.50
AI1 input voltage
protection lower
limit
0.00V to F7.51
3.1V
☆
254
F7.51
AI1 input voltage
protection upper
limit
F7.50 to 10.00V
6.8V
☆
5-1-10.F8 Group - Fault and protection
No.
Code
Parameter name
Setting range
Factory
setting
Cha
nge
255
F8.00 Overcurrent stall gain 0 to 100
20
☆
256
F8.01
Overcurrent stall
protection current
100% to 200%
-
☆
257
F8.02
Motor overload
protection selection
0: Invalid 1: Enable
1
☆
258
F8.03
Motor overload
protection gain
0.20 to 10.00
1.00
☆
259
F8.04
Motor overload pre-
alarm coefficient
50% to 100%
80%
☆
260
F8.05
Over-voltage stall
gain
0 to 100
0
☆
261
F8.06
Over-voltage stall
protection voltage /
energy consumption
brake voltage
120% to 150%
130%
☆
262
F8.07
Input phase loss
protection selection
Units digit:Input phase loss protection
selection
0: Invalid 1: Enable
Tens digit:contactor actuation protection
0: Invalid 1: Enable
11
☆
263
F8.08
Output phase loss
protection selection
0: Invalid 1: Enable
1
☆
264
F8.09
Short to ground
protection
0:Invalid 1: Valid
1
☆
265
F8.10
Number of automatic
fault reset
0 to 32767
0
☆