Chapter 5 Function parameter
71
Ch
ap
ter 5
Pulse frequency can be inputted into the inverter only through DI5 channel. The application
on this group of functions is similar to curve 1, please refer to the description of curve 1.
F1.30
DI filter time
0.000s
~
1.000s
0.010s
☆
Set software filter time for DI terminals status. For the application that input terminals are
vulnerable to interference and cause the accidental operation, you can increase this parameter so as
to enhance the anti-interference ability. However, the increase of filter time will cause DI terminal
slow response.
F1.31
AI1 filter time
0.00s
~
10.00s
0.10s
☆
F1.32
AI2 filter time
0.00s
~
10.00s
0.10s
☆
F1.33
Panel encoder/AI3
filter time
0.00s
~
10.00s
0.10s
☆
F1.34
HDI filter time
0.00s
~
10.00s
0.00s
☆
F1.35
DI terminal Mode
Selection 1
Units digit
DI1 Terminal active state set
00000
★
high level active
0
Low level active
1
Tens digit
DI2 Terminal active state set
(0~1,same as the units digit)
Hundreds digit
DI3 Terminal active state set
(0~1,same as the units digit)
Thousands digit
DI4 Terminal active state set
(0~1,same as the units digit)
Ten thousands
digit
DI5 Terminal active state set
(0~1,same as the units digit)
F1.36
DI terminal mode
selection 2
Units digit
DI6 Terminal active state set
00000
★
high level active
0
Low high level active
1
Tens digit
DI7 Terminal active state set
(0~1,same as the units digit)
Hundreds digit
DI8 Terminal active state set
(0~1,same as the units digit)
Thousands digit
DI9 Terminal active state set
(0~1,same as the units digit)
Ten Thousands
digit
DI10 Terminal active state set
(0~1,same as the units digit)
For setting the digital input terminal of the active mode. When selecting high effective,
appropriate DI terminal and COM communicated effectively, disconnect invalid. Select is low
effective, appropriate DI terminal and COM connectivity invalid, disconnect effective
。
F1.37 DI1 delay time
0.0s
~
3600.0s
0.0s
★
F1.38 DI2 delay time
0.0s
~
3600.0s
0.0s
★
F1.39 DI3 delay time
0.0s
~
3600.0s
0.0s
★
DI terminal for setting status changes, changes in the delay time of the inverter.
Currently only DI1, DI2, DI3 with delay time setting function.
F1.42 Keyboard potentiometer X2
0
~
100.00%
0.50%
☆
Keyboard potentiometer set value end point