Chapter 4 Installation and commissioning
4-1.Installation direction and space
PI500-E series inverter according to different power rating, the requirements of around
installation reserve space is different , specifically as shown below
:
Power rating
Dimension requirement
0.75
~
7.5kW
A≥100mm
;
B≥10mm
11
~
22kW
A≥200mm
;
B≥10mm
30
~
75kW
A≥200mm
;
B≥50mm
90
~
400kW
A≥300mm
;
B≥50mm
Figure 4-1: PI500-E series each power level installation space requirement
PI500-E Series frequency inverter heat radiator circulated from bottom to top, when more
than one inverter work together, usually mounted side by side. In the case of the need to install
them by upper and lower rows, due to the heat of the lower inverters rising to the upper equipment,
fault maybe caused, heat insulation deflector and other objects to be installed.