Chapter 5 Function parameter
68
Code
Parameter name
Setting range
Factory
default
Change
When the set frequency is within the jump frequency range, the actual running
frequency will be the boundaries of the jump frequency.
The inverter can avoid mechanical resonance point of load by setting jump frequency.
This inverter can set 1 jump frequency point. If the jump frequency points are set to 0,
this function does not work.
1/2*跳跃幅度
1/2*跳跃幅度
时间(t)
设定频率(f)
跳跃频率
跳跃频率示意图
F7.07
Jump frequency availability
during ac/deceleration
process
Invalid
0
0
☆
Valid
1
The function code is used to set whether the jump frequency is active or not in the
process of acceleration and deceleration.
If it is set to active, when the operating frequency is in the jump frequency range, the
actual operating frequency will skip the set jump frequency boundary.
1/2*跳跃幅度
1/2*跳跃幅度
时间(t)
设定频率(f)
跳跃频率
加减速过程中跳跃频率有效示意图
F7.08
Forward/reverse
rotation
deadband
0.0 to 3600.0s
Depends on
models
☆
Set frequency (f)
Jump
frequency
1/2* Jump amplitude
1/2* Jump amplitude
Time(t)
Schematic diagram of jump frequency valid in the process of acceleration.
Time(t)
Schematic diagram of jump frequency
Set frequency (f)
1/2* Jump amplitude
1/2* Jump amplitude
Jump
frequency