Chapter 5 Function parameter
66
Code
Parameter name
Setting range
Factory
default
Change
F6.01
Running status display
parameters selection
0 to 0xFFFF
BIT0: Running frequency
BIT1: Set frequency
BIT2: Bus voltage
BIT3: Output voltage
BIT4: Output current
BIT5: Running speed
BIT6: Output power
BIT7: Output torque
BIT8: PID setting value
BIT9: PID feedback value
BIT10: Input terminal status
BIT11: Output terminal status
BIT12: Analog AI1 value
BIT13: Analog AI2 value
BIT14: Current stage of multi-
speed
BIT15: Torque set value
03FF
☆
When the inverter is in operation, the parameter display is limited by F6.01, that is
16-bit binary string, if a bit is 1, the parameters corresponding to the bit can be viewed
by SHIFT key during operation. If a bit is 0, the parameters corresponding to the bit
will not display. To set function code F6.01, a binary number must be converted into a
hexadecimal number, and then enter the function code.
F6.02
Stop status display
parameters selection
1 to 0x3FF
BIT0: Set frequency
BIT1: Bus voltage
BIT2: Input terminal status
BIT3: Output terminal status
BIT4: PID setting value
BIT5: PID feedback value
BIT6: Analog AI1 value
BIT7: Analog AI2 value
BIT8: Current stage of multi-
speed
BIT9: Torque set value.
BIT10 to BIT15: Reserved
0FF
☆
The setting on this function is same with F6.01 setting. When PI130 series inverter
stops, the parameters display is effected by this function code.
F6.03
Speed display
coefficient
0.1 to 999.9%
Mechanical speed = 120 *
running frequency *
F6.03/number of motor pole
pairs.
100.0%
☆
Mechanical speed = 120 * running frequency * F6.03/number of motor pole pairs, this
function code is used to correct speed scale display error, has not affect to the actual
speed.