Chapter 5 Function parameter
37
No. Code
Parameter name
Setting range
Factory
default
Change
Reference
page
5: odd parity (O, 8, 2) for
RTU
6: no parity (N, 7, 1) for
ASCII
7: even parity (E, 7, 1)
for ASCII
8: odd parity (O, 7, 1) for
ASCII
9: no parity (N, 7, 2) for
ASCII
10: even parity (E, 7, 2)
for ASCII
11: odd parity (O, 7, 2)
for ASCII
12: no parity (N, 8, 1) for
ASCII
13: even parity (E, 8, 1)
for ASCII
14: odd parity (O, 8, 1)
for ASCII
15: no parity (N, 8, 2) for
ASCII
16: even parity (E, 8, 2)
for ASCII
17: odd parity (O, 8, 2)
for ASCII
126.
F9.02
Communication
address of this unit
1 to 247, 0 for broadcast
address
1
☆
74
127.
F9.03
Communication
response delay
0 to 200ms
5ms
☆
74
128.
F9.04
Communication
timeout fault time
0.0 (Invalid
)
;
0.1 to 100.0s
0.0 s
☆
74
129.
F9.05
Data transfer
format selection
0: non-standard
MODBUS protocol
1: standard MODBUS
protocol
2: ASCII
0
☆
75
130.
F9.06
Transmission error
handling
0: Alarm and free stop
1: No alarm and continue
to run
2: No alarm and stop at
the selected mode (under
1
☆
75