Chapter 5 Function parameter
87
5-2-18.b0 Group - Motor parameter group
Code
Parameter name
Setting range
Factory
default
Change
b0.00
Inverter type
0.G type (constant torque
load type)
1: Reserved
0
★
b0.011 Rated motor power
0.4 to 900.0kW
Depends on
models
★
b0.02
Rated motor voltage
0 to 460V
Depends on
models
★
b0.03
Rated motor current
0.1 to 2000.0A
Depends on
models
★
b0.04
Rated motor frequency 0.01Hz to F0.08 (maximum
output frequency)
50.00Hz
★
b0.05
Rated motor speed
0 to 36000rpm
Depends on
models
★
Note: please set up according to the motor nameplate parameters. The excellent
vector control performance needs the accurate motor parameters.
The inverter provides the function of parameter auto tunning. The accurate
parameter auto tunning depends on correctly inputing parameters on the motor
nameplate.
In order to guarantee the control performance, please try to ensure that the inverter
power matches the motor power, if the gap between the two is too large, the inverter
control performance will be significantly reduced.
Note: Resetting the motor rated power (b0.01) will initialize motor parameters
b0.06 to b0.10.
b0.06
Motor stator resistance 0.001 to 65.535Ω
Depends on
models
☆
b0.07
Motor rotor resistance 0.001 to 65.535Ω
Depends on
models
☆
b0.08
Motor stator and rotor
inductance
0.1 to 6553.5mH
Depends on
models
☆
b0.09
Motor stator and rotor
mutual inductance
0.1 to 6553.5mH
Depends on
models
☆
b0.10
Motor no-load current 0.01 to 655.35A
Depends on
models
☆
When the motor parameter auto tunning is competed, the set value of b0.06 to
b0.10 will be automatically updated. These parameters as the basis of high-
performance vector control have a direct impact on the control performance.