background image

20 - 80 kVA parallel UPS systems

User’s and Installation Manual

1018390
Revision  C

37

7.5 Signal inputs

The programmable auxiliary inputs are used to control the operation of UPS modules. A
double shielded cable is the best alternative but single shielded twisted multipair cable is
also usable. Remember that signals should not have a galvanic connection to any mains
connected circuits.

Emergency Power Off (EPO)

The emergency shut down wiring is connected to the terminal X4 with maximum resistance
of 10 ohm. It can also be used for a remote shut down in the event of a room
overtemperature by thermal relay. EPO terminals must not be connected in series with the
parallel system configuration. Internal EPO circuits require a galvanic isolation of the
signals.

The terminal X4 is a ‘normally closed’ type of connection. Hence, the logic circuitry will
immediately shut down the UPS module when the connection is open. The terminal X4 has
to be shorted to keep the UPS module running. A manual start is needed to make the UPS
module run again after the emergence power off mode.

Generator On

Auxiliary contact wires of a generator control device are connected to the terminal X219. It
is used for inhibiting the transfer to static bypass line when the UPS module is supplied from
an unstable AC source. The information has to be connected to all parallel UPS modules.

The terminal X219 is a ‘normally open’ type of connection. Hence the logic circuitry will
prevent the transfer to unstable power source when the connection is closed. UPS modules
are delivered the connection open on the terminal X219.

Remote Output On/Off

The remote output on/off wiring is connected to the terminal X220. It can be used to turn
off the UPS module output from a distance.

The terminal X220 is a ‘normally open’ type of connection. Hence the logic circuitry will
turn off the inverter when the connection is closed. In order to turn on the inverter the
connection between these pins has to be open.

System Bypass Switch

The auxiliary contact wiring of the system bypass switch is connected to the terminal X221.
The information has to be connected to all parallel UPS modules. Make sure that the
polarity of the auxiliary contact wiring is the same for all UPS modules.

In parallel UPS systems this signal must be connected to the auxiliary contact information of
the system bypass switch in the tie panel.

The terminal X221 is a ‘normally open’ type of connection. Hence the logic circuitry will
transfer the UPS modules to internal bypass line when the connection is closed.

Environment Alarm

The building alarm wiring is connected to the terminal X222. For example, it can be used
for overtemperature or smoke detector alarms.

The terminal X222 is a ‘normally open’ type of connection. Hence the logic circuitry will
indicate to the user through the RS-232 when the connection is closed.

Содержание 9305 HS Series

Страница 1: ...User s and Installation Manual 20 80 kVA parallel UPS systems...

Страница 2: ......

Страница 3: ...4 5 1 Overview 14 5 2 Placing UPS modules 15 5 3 Placing battery cabinets 17 6 Electrical installation 18 6 1 Overview 18 6 2 Location of terminals 18 6 3 Input and output power cables 19 6 4 Parallel...

Страница 4: ...her and may not be reproduced even extracts unless permission granted Every care has been taken to ensure the accuracy of the information contained in this manual but no liability can be accepted for...

Страница 5: ...e fuses from the selected line for extra safety precaution Make absolutely sure that there is no power connected to UPS modules Warning The parallel UPS system must be installed according to the instr...

Страница 6: ...umes Operation of the electrical equipment in such an environment constitutes a safety hazard The only user operations permitted are Starting up and shutting down the UPS unit not the initial start up...

Страница 7: ...e 1 A parallel configuration constructed with four UPS modules Always remember that the parallel UPS system is connected to the AC mains power and contains internal high current batteries for back up...

Страница 8: ...PS modules of the parallel system share equally the load with Hot Sync technology The parallel outputs are combined in a System Parallel Module or cabinet It is the system component containing the obl...

Страница 9: ...ery bank The UPS will start up again automatically providing power to the critical load and charging the battery bank when the mains voltage is restored Figure 3a Block diagram of UPS module A double...

Страница 10: ...ine when the inverter is overloaded or the inverter is not able to feed the load The output is protected with a tripping circuit breaker to separate the faulty UPS module from the parallel load bus Th...

Страница 11: ...shipping and packing materials should be stored for further investigation if damage has occurred during the transportation The equipment must be inspected for shipping damage A claim must be filed im...

Страница 12: ...rson shall perform the following procedure and tests during the start up the new parallel UPS system 1 Visual inspection Make a visual inspection of the equipment for signs of damage or foreign materi...

Страница 13: ...continuously controls the condition of the battery bank Battery failure alarm is activated when the capacity of the battery bank has decreased remarkable from the default value Scrapping Before scrapp...

Страница 14: ...Revision C 14 5 Mechanical installation 5 1 Overview Environmental requirements and restrictions described in the technical specification shall be met to guarantee the proper function and safety of th...

Страница 15: ...t n i o P m c g k 2 g n i d a o l d e t u b i r t s i D m g k 2 s e i r e t t a b o w S P U A V k 0 3 0 2 0 1 2 1 3 0 2 5 s e i r e t t a b s c p 2 3 x 2 h t i w S P U A V k 0 3 0 2 0 0 4 9 5 5 6 2 1...

Страница 16: ...e 6b Ventilation and space requirements for 40 80 kVA UPS Power cables shall be routed from the bottom or rear side of the UPS modules The cables shall be protected with a casing tube The size and loc...

Страница 17: ...hall have the external battery cabinets on the left or right side External battery cabinets shall be connected together by using narrow metal plates provided with external battery cabinets The externa...

Страница 18: ...ltage and current that can injure or kill personnel and damage equipment Input and output power cables must be selected according to local regulations and installation environment The recommendations...

Страница 19: ...nd the rated current of the UPS module An internal circuit breaker is used to protect the input bridge and power semiconductors Table 2 Recommended input output cables and fuses of parallel UPS module...

Страница 20: ...late 40 80 kVA 6 5 Battery cables Located behind the door the external battery connection N and PE is used with BAT D BAT E and BAT F cabinets Each shipment of external battery cabinets includes 16 mm...

Страница 21: ...0 kVA parallel UPS systems User s and Installation Manual 1018390 Revision C 21 Figure 12 Wiring diagram of the external battery cabinets D and E Figure 13 Wiring diagram of the external battery cabin...

Страница 22: ...configurations with 40 80 kVA UPS modules Power cables should be connected to the battery terminals of the UPS modules See the battery wiring diagrams and chapter Location of terminals for the correct...

Страница 23: ...o i t p i r c s e D 2 5 8 9 1 0 1 2 0 3 1 0 4 3 9 5 0 3 9 M P S s e l u d o m A V k 0 3 1 0 8 S P U x 2 1 r o f t e n i b a c M P S g n i d n a t s r o o l F 0 5 8 9 1 0 1 4 0 8 5 0 3 9 M P S s e l u...

Страница 24: ...r the shared load bus It also enables the make before break transfer of the load to the system bypass This can be used for service or test purposes The available SPM tie cabinets have the following ma...

Страница 25: ...kVA parallel UPS systems User s and Installation Manual 1018390 Revision C 25 Figure 17 Cable routing of SPM9305 9340 130 2 and SPM9305 80 4 tie cabinets Figure 18 Cable routing of SPM9305 60 4 tie ca...

Страница 26: ...20 80 kVA parallel UPS system User s and Installation Manual 1018390 Revision C 26 Figure 19 Wiring diagram with SPM9305 9340 130 2 tie cabinet...

Страница 27: ...20 80 kVA parallel UPS systems User s and Installation Manual 1018390 Revision C 27 Figure 20 Wiring diagram with SPM9305 60 4 and SPM9305 80 4 tie cabinets...

Страница 28: ...ground Notice UPS modules should get a minimum of 10 ms leading closed contact signal when the system bypass switch is turned from UPS to BYPASS position e p y T g n i t a r S P U g n i t a r s s a p...

Страница 29: ...20 80 kVA parallel UPS systems User s and Installation Manual 1018390 Revision C 29 Figure 21 Cable routing and mounting holes for SPM9305 60 2 and SPM9305 30 2 tie cabinets...

Страница 30: ...20 80 kVA parallel UPS system User s and Installation Manual 1018390 Revision C 30 Figure 22 Location of SPM9305 60 2 and SPM9305 30 2 control switches...

Страница 31: ...90 Revision C 31 Figure 23 Wiring diagram with SPM9305 30 2 tie cabinet Table 5 Recommended cables and fuses for the wiring diagram r e w o P 1 e s u F 2 e s u F B A e l b a C D C e l b a C A V k 0 2...

Страница 32: ...e cabinet Table 6 Recommended cables and fuses for the wiring diagram r e w o P 1 e s u F 2 e s u F 3 e s u F B A e l b a C C e l b a C D e l b a C A V k 0 4 A 3 6 A 0 0 1 A 5 2 1 m m 6 1 m m 0 5 m m...

Страница 33: ...ition 2 Auxiliary contacts provide 10 ms leading signal with a closed contact 3 One should check from the LCD panels that UPS modules are not unsyncronised and the signal wiring polarity is correct 4...

Страница 34: ...ng configuration Cables are delivered with the UPS modules 6 Since the UPS does not have automatic backfeed isolation a warning label must be added on all primary power isolators installed remote from...

Страница 35: ...to the UPS modules Software can control or monitor UPS modules individually not as a parallel system Check from the software documentation that the platform running on your computer is supported Use n...

Страница 36: ...h a maximum rating of 1A 30VAC or 0 2A 60VDC They have a complete galvanic isolation from the other UPS circuits according to IEC60950 and EN50091 1 It is recommended that the relay output signals run...

Страница 37: ...nnected to all parallel UPS modules The terminal X219 is a normally open type of connection Hence the logic circuitry will prevent the transfer to unstable power source when the connection is closed U...

Страница 38: ...unit will function properly can not be guaranteed During commissioning the manufacturer representative will train the users to operate the parallel UPS system 8 2 Start up procedure Check that the pa...

Страница 39: ...modules have started 8 Check that service switches of the SPM9305 or local tie panel are in the ON position 9 Transfer the critical load to UPS modules by turning the system bypass switch to UPS posi...

Страница 40: ...ronised to mains Following procedure does returning to normal online mode 1 Make sure UPS modules have been started according to chapter Start up procedure 2 Check that UPS ON and BYPASS LED s are lit...

Страница 41: ...es not contain the system bypass switch 3 Turn the main switch S1 to the OFF position 4 Turn off the battery circuit breakers F2 and F4 20 30 kVA UPS modules with ext BAT cabinets 5 Turn off the main...

Страница 42: ...it when a situation in the UPS requires immediate action Figure 29 Control panel and LED status indications 8 6 Control panel displays Normal display The Normal display shows the UPS type The panel au...

Страница 43: ...if there is some abnormal operation in the unit If there is active alarm in the unit it will be indicated on the bottom row Pressing button will transfer the display to Active Alarms display Here all...

Страница 44: ...cate the 8 latest alarms of the UPS and also the time when each alarm has happened The time showed days hrs min sec is the time between consecutive alarms The alarms can be viewed by pressing the butt...

Страница 45: ...ion in case of power problems The alarm messages are used together with the events logger as part of a diagnostic system for the UPS service specialist Battery power is used when the rectifier cannot...

Страница 46: ...C r o e n O y l p p u s r e w o p e b y a m s e s u f e r o m y d o b e m o s r o n w o l b e v a h t n e d i c c a y b d l u o c y l p p u s e h t f f o d e h c t i w s T E N I B A C E R U T A R E P...

Страница 47: ...Hz 2 4 Frequency range for rectifier 45 65 Hz 2 5 Nominal max input current 20 kVA 3 x 21 A 3 x 30 A 30 kVA 3 x 36 A 3 x 45 A 40 kVA 3 x 47 A 3 x 65 A 50 kVA 3 x 60 A 3 x 80 A 60 kVA 3 x 70 A 3 x 93...

Страница 48: ...P U f o r N A V k 0 2 s e l u d o m A V k 0 3 s e l u d o m A V k 0 4 s e l u d o m A V k 0 5 s e l u d o m A V k 0 6 s e l u d o m A V k 0 8 s e l u d o m S P U x 2 A V k 0 4 A V k 0 6 A V k 0 8 A V...

Страница 49: ...2 x 2 s e i r e t t a B h A 4 2 x 4 2 x 2 h A 8 3 x 4 2 x 2 h A 5 6 x 4 2 x 2 t h g i e W g k 0 5 5 g k 5 1 8 g k 0 9 3 1 h t d i W m m 2 8 3 m m 0 2 5 m m 4 3 0 1 m m h t p e D m m 8 8 7 m m 8 8 7 m...

Страница 50: ...20 80 kVA parallel UPS system User s and Installation Manual 1018390 Revision C 50 Appendix A Dimension drawings 20 30 kVA UPS...

Страница 51: ...20 80 kVA parallel UPS systems User s and Installation Manual 1018390 Revision C 51 Appendix B Dimension drawings 40 80 kVA UPS...

Страница 52: ...20 80 kVA parallel UPS system User s and Installation Manual 1018390 Revision C 52 Appendix C Dimension drawings SPM9305 Ref SPM9305 80 4 SPM9305 60 4 SPM9305 9340 130 2...

Отзывы: