20 - 80 kVA parallel UPS systems
User’s and Installation Manual
1018390
Revision C
47
11. Technical specifications
1. General
1.1 Rated power
20 kVA, 30 kVA, 40 kVA, 50 kVA, 60 kVA, 80 kVA;
at p.f. 0,7, inductive or non linear load
1.2 Technology
Double conversion online topology with automatic
bypass switch and maintenance bypass switch.
Voltage and Frequency Independent operation:
Class VFI-SS-111 by IEC 62040-3
2. Input
2.1 Rated voltage
220/380, 230/400, 240/415 Vac; three phase input
(3xL+N+PE)
2.2 Voltage range
170/294-279/484 VAC without depleting battery 20-50 kVA
and 80 kVA
180/312-279/484 VAC without depleting battery 60 kVA
196/336-279/484 VAC full charge capability
2.3 Rated frequency
50/60 Hz
2.4 Frequency range for rectifier
45 - 65 Hz
2.5 Nominal/max input current
20 kVA 3 x 21 A / 3 x 30 A
30 kVA 3 x 36 A / 3 x 45 A
40 kVA 3 x 47 A / 3 x 65 A
50 kVA 3 x 60 A / 3 x 80 A
60 kVA 3 x 70 A / 3 x 93 A
80 kVA 3 x 97 A / 3 x 125 A
2.6 Input power factor
> 0.96 (Cosphi 1)
3. Output
3.1 Nominal voltage
220/380, 230/400, 240/415 VAC, selectable
3.2 Voltage regulation
< ± 1% static
< ± 1% with 100% unbalanced load
< ± 5% dynamic at 100% load change
Recovery time < 1 ms
3.3 Voltage distortion
< 1 % THD linear load
< 5 % THD non linear load
3.4 Frequency
50/60 Hz, selectable
3.5 Frequency regulation
Synchronisation to line, ± 0.5, ± 1.0 or
± 2.0 Hz selectable.
Free-running ± 0.05 Hz
Slew rate 0.5, 2.5, 6 Hz/sec, selectable
3.6 Over load
101% to 110% for 10 minutes (online)
111 - 125% for 60 sec (online)
126 - 150% for 30 sec (online)
151 - 170% for 5 sec (online)
125% continuous (bypass)
1000% for one cycle (bypass)
3.7 Parallel load sharing
±5% of the rated load