2. Installation
Installation and wiring must be performed in accordance with the local
electric code and the following instructions by professional personnel.
For safety, please cut off the mains power switch before installation.
The battery breaker also needs to be cut off if it is a long backup time
model (
“
XL
”
model).
1) Open the terminal block cover located on the rear panel of the
UPS, please refer to the appearance diagram.
2) For
UPS, it is recommended to select the UL1015
10AWG(6mm
2
) wire or other insulated wire which complies
with AWG Standard for the UPS input and output wirings.
3) For
UPS, it is recommended to
select the UL1015 8AWG (10mm
2
) wire or other insulated
wire which complies with AWG Standard for the UPS input
and output wirings.
4) For
UPS
,
it is recommended
to select
the UL1015
6AWG(25mm
2
)
wire
or
other
insulated wire
which com lies with AWG Standard for the UPS input and
output wirings.
Note:
Do not use the wall receptacle as the input power source for
the UPS, as its rated current is less than the UPS
’
s maximum
input current. Otherwise the receptacle may be burned and
destroyed.
5) Connect the input and output wires to the corresponding input
and output terminals according to the following diagram.
Note:
you must make sure that the input and output wires and the
input and output terminals are connected tightly.
6) The protective earth ground wire refers to the wire connection
between the equipment which consumes electric equipment
and the ground wire. The wire diameter of protective earth
ground wire should be at least as above mentioned for each
model and green wire or green wire with yellow ribbon wire is
used.
6KT-XL
10KT-XL/3C10KT-XL
3C15KT-XL/3C20KT-XL
Содержание 10KT
Страница 23: ...Wiring diagram of 6KT XL 0KT XL 1 parallel system...
Страница 24: ...Wiring diagram of 3C 1 KT XL 0 parallel system...
Страница 25: ...Wiring diagram of 3C 15KT XL 20KT XL parallel system 3C...
Страница 48: ...STEP 5 The output voltage would be 230VAC after the UPS is turned on...
Страница 50: ...DB 9 Interface of AS400 communication protocol...
Страница 53: ...Appendix 2 Rear Panel Back view of 6KVA Back view of 6KVA XL Back view of 10KVA Back view of 10KVA XL...
Страница 54: ...10KVA Back View of 31 Back View of 31 20KVA...
Страница 55: ......