38
-
The display of battery test mode is same as Battery mode, but
“
H
”
and
“
L
”
would not be shown unless the input line voltage is higher
or lower than the SPEC range during the time of battery test. The
operating mode code of the UPS is
“
03
”
in Battery mode, and the
code is
“
04
”
in Battery Test mode.
10.5 Parallel mode
The LCD display can show the UPS quantity of the parallel system,
and the UPS system that operating in single mode should be
regarded as a special parallel system, single mode is a special
parallel mode.
The LCD display in parallel mode is shown in the following
diagram. When the UPS operating in parallel mode, the
information in code display alternates between symbol
“
Pn
”
and
Mode code. The symbol
“
P
”
means the UPS operating in parallel
mode, and the number
“
n
”
indicate the quantity.
10.6 Warning mode
The LCD display in warning mode is shown in the following
diagram. The information about the utility power, the battery, the
UPS output and the load could be displayed. The symbol
“
MODE
”
not be shown and the symbol
“
WARNING
”
is shown instead in
code display.
Parallel mode
Содержание 10KT
Страница 23: ...Wiring diagram of 6KT XL 0KT XL 1 parallel system...
Страница 24: ...Wiring diagram of 3C 1 KT XL 0 parallel system...
Страница 25: ...Wiring diagram of 3C 15KT XL 20KT XL parallel system 3C...
Страница 48: ...STEP 5 The output voltage would be 230VAC after the UPS is turned on...
Страница 50: ...DB 9 Interface of AS400 communication protocol...
Страница 53: ...Appendix 2 Rear Panel Back view of 6KVA Back view of 6KVA XL Back view of 10KVA Back view of 10KVA XL...
Страница 54: ...10KVA Back View of 31 Back View of 31 20KVA...
Страница 55: ......