36
-
The UPS does not have the backup function when it is in Bypass
mode. The power used by the load is supplied from the utility
power via internal filter.
10.3 Line mode
The LCD display in Line mode is shown in the following diagram.
The information about the utility power, the battery, the UPS output
and the load could be displayed. The block of
“
INVERTER
”
indicates the inverter is working. The operating mode code of the
UPS is
“
02
”
.
If output overloaded, the load percent is shown and alarm will keep
twice every second. You should get rid of some unnecessary loads
one by one to decrease the loads connected to the UPS less than
90% of its nominal power capacity.
Note:
Please follow the following steps to connect the generator
:
●
Activate the generator and wait until the operation is stable
before supplying power of the generator to the UPS (be sure
that the UPS is in idle mode). Then turn on the UPS according
to the start-up procedure. After the UPS is turned on, then the
loads can be connected to the UPS one by one.
Line mode