2.1.3
Which configurations are supported?
Your PQube 3 can monitor circuits anywhere in the world (single-phase all the way up to 3-phase).
It supports nominal voltages up to 960VAC phase-to-phase (600 VAC phase-to-earth) and mains
frequencies of 16.7 Hz, 50 Hz, 60 Hz, and 400* Hz. For medium and high voltage applications, your
PQube 3 supports PT and CT ratios up to 50000:1.
Your PQube 3 can also be used to monitor DC voltage, which can be useful for solar applications
(monitor the AC and DC voltages of your inverter).
*coming soon! Contact PSL for free firmware upgrade!
2.1.4
How do I power my PQube 3?
It can be directly powered from 24V AC or 24~48V DC or Power over Ethernet (PoE), or it can be
equipped with an optional snap-in PM1 Module that operates from AC 100V ~ 240V, 50/60/400
Hz. You can also apply DC 120V ~ 370V too!
2.1.5
How do I communicate with my PQube 3?
No network is required to retrieve files from your PQube 3. Simply copy the data to your computer
using a USB thumb drive or microSD card.
If you have a network connection available, your PQube 3 can automatically send you e-mails
whenever it detects an event. You can send your PQube 3 a new setup file, or even update its
firmware via e-mail. It also includes a built-in web server, FTP server, and supports communication
protocols including MODBUS TCP/IP, SNMP and more, giving you many ways to communicate with
your PQube 3.