Advanced:
UPS battery status and GPS synchronization status are available here.
Coming soon! You will be able to view status of your signal relay(s) and your PM2’s
24V auxiliary outputs.
Meters
5.1.1.2
Voltage and Frequency:
These are line-to-line, line-to-neutral, and neutral-to-earth
true-RMS voltmeters. Different meters will show on these screens, depending on
your power configuration. (For example, if the power configuration is “delta”, there
will not be any L-N meters, because there is no neutral conductor.) If you have set a
potential transformer ratio in your
Setup.ini
file, the values will reflect this ratio.
Current:
These meters show the true-RMS current. If you have set a current
transformer ratio in your
Setup.ini
file, then these meters will use that ratio, so
these meters will sometimes show their values in kilo-amps or even mega-amps.
Different meters will show on this screen, depending on your power configuration.
(For example, if the power configuration is “delta”, this screen will not show a
neutral current meter, because there is no neutral conductor in delta power.)