PQube 3 Instruction Manual
Page 75 of 103
KYZ_Relay_in_Wh_per_Pulse=0
Energy output KYZ, expressed in Watt-hour per
pulse.
0 (to disable output)
Any number
Record_IEC_61000-4-30_10_Min_Interval=OFF
Enable 10-minute and 2-hour interval trend
recordings in a separate CSV file, per the
requirements of IEC 61000-4-30 Class A.
ON
OFF
Enable_10_Second_Frequency=OFF
Default setting is OFF. With OFF setting, the
frequency measurement interval is 1 second.
Set this tag ON to change the frequency interval
to 10 seconds, per the methods in IEC 61000-4-30
Class A Clause 5.1
ON
OFF
Record_2-150kHz_Conducted_Emissions=ON
Toggles the 2-150kHz daily trend file generation.
ON
OFF
Current_Range="LOW"
For currents,
HIGH range = ±10V peak
LOW range = 0.333Vrms
HIGH
LOW
Flicker_Lamp_Voltage=230
Sets the lamp voltage rating for your flicker
measurements, per the requirements of IEC
61000-4-15 Ed. 2 Class F1.
Your PQube sets the response curve based on the
lamp voltage rating and nominal frequency.
120
230
[Potential_Transformers]
This allows you to express amplitudes measured
at the primary of the transformer.
Potential_Transformer_Ratio=1:1
You can use fractional values such as 1250.5:120.
The PT ratio will appear on the display, webpage,
and the CSV header.
If the PT ratio is high enough, your PQube will
automatically switch the units to kV or MV.
From
1:1
to
50000:1
Potential_Transformer_Ratio=
14400:120
[Current_Transformers]
Allows you to express the amplitude of currents
measured at the primary of the current