PQube 3 Instruction Manual
Page 73 of 103
You can also manually set the frequency to 50, 60,
or any frequency between 320 and 560Hz.
to 16.67Hz)
50
60
Any number between
320 to 560
[Channel_Recordings]
Generate_GIF_Graphs=ON
Generate_PQDIF_Files=ON
Choose the types of files your PQube will
generate for events and trends
; ------ Valid Values: ON, OFF
Recorded_Samples_Per_Cycle=256
; ------ Choose the number of samples/cycle for
waveform recordings
; ------ This does not change your PQube 3's
sampling rate, only the level of detail in your
waveform graphs. Your PQube 3 always samples
at 512 samples/cycle.
; ------ Your choice is a tradeoff between graph
resolution and the overall number of cycles
displayed in the graph.
; ------ Valid Values: 32, 64, 128, 256, 512. Typical
value 256
; ------ There are 4096 total samples in the
waveform buffer. Your PQube records 8 cycles at
value 512, 16 cycles at value 256, ..., 128 cycles at
value 32
Record_Phase_To_Phase_Channels=AUTO
Record_Phase_To_Neutral_Channels=AUTO
If your Power Configuration includes a neutral
conductor, your PQube will automatically be set
to record Phase-Neutral channels.
If your Power Configuration includes multiple
phases, it will automatically record Phase-Phase
channels in the Meters (on display, webpage, and
AUTO
ON
OFF