Installation and operator’s manual
Page 51 of 65
PVI-2000-OUTD-AU Rev.: 1.0)
Fig.17 Multiple units connection daisy-chain style
NOTE
:
When using the RS-485 link there can be no more than 31 inverters
connected on the same link. Although you are free to choose any address
between 2 and 63, we recommend using addresses between 2 and 34 for the
RS-485 serial link.
NOTE
When using the RS-485 link, in case one or more inverters are later
added to the system; please remember to bring the dip switch that was the
last of the system back to OFF.