Installation and operator’s manual
Page 13 of 65
PVI-2000-OUTD-AU Rev.: 1.0)
WARNING
: String voltage shall not exceed 600 Vdc for any reason, to prevent any
damage to the equipment
NOTE:
The minimum required input voltage for start the initial grid connection
sequence is 200Vdc.
When Aurora is connected, it will export energy on the grid since the input range will
remain between 90Vdc and 580Vdc.
The total current of an array must also be within the capability limits of the inverter.
The 2000W model of AURORA is capable of handling a single array and the
maximum input current can be 10Adc.
In case the photovoltaic system exceeds the capabilities of a single AURORA inverter,
additional inverters can be added to the system, each connected to a suitable section of
the photovoltaic field on the Dc side, and to the grid on the Ac side.
Each AURORA inverter will work independently from the others and will push to the
grid the maximum power available from its own section of the photovoltaic panels.
The actual decisions on the way the photovoltaic system is structured and wired
depend on a number of factors and considerations, such as type and model of panels,
available area, location, energy targets, as well as on good design practices.
Power-One provides a system configuration tool on its website (
www.power-one.com
)
that can assist in modelling the system.
Fig.3 Simplified diagram of a photovoltaic system