Installation and operator’s manual
Page 20 of 65
PVI-2000-OUTD-AU Rev.: 1.0)
3.3
Choosing installation location
The location for the installation of AURORA should be selected in accordance to the
following recommendations:
¾
AURORA should be placed at a suitable height from the ground to allow easy
reading of the front display.
¾
Leave enough room around the unit to allow easy installation and maintenance
(Fig 5).
¾
Choose a location sheltered from sun radiation and able to provide some
ventilation.
¾
The screw and tabs for wall mounting need to be chosen according to the wall
construction material (stone, full bricks, holed bricks, etc).
WARNING
: The metal surface in the back of AURORA could reach high
operating temperatures (
up to 70°C
). Avoid contact of the surface with
materials that are flammable or sensitive to high temperature (wallpaper,
fabrics, wood, etc.)
Fig.5 Installation location
500mm (18”)
500mm (18”)
>100mm
(4”)
>300mm
(12”)