Install room units in the main occupancy rooms. The place of installation should be
chosen so that the sensor can capture the room temperature as accurately as possible
without getting adversely affected by direct solar radiation or other heat or refrigeration
sources (about 1.5 metres above the floor)
The base provides the power for QAA55 and QAA75. When the units are removed
from their base, power is cut off (i.e. the units are out of operation).
Connections:
5.4 INSTALLING ROOM AND OUTSIDE TEMPERATURE SENSORS
5.4.1. Locating Room Thermostat Units (all types)
Siemens QAA55/58
Siemens QAA75/78
Terminal
Designation
QAA55
QAA75
1
2
3
CL+
CL-
G+
BSB data
BSB ground
Not used
BSB data
BSB ground
Power supply DC 12V
a
a