0 - 10V direct heating circuit temperature control (H2 Expansion Modules 1-3)
The operation and flow temperature output of the boiler can be controlled directly
using a 0 - 10VDC signal. Once activated, the boilers will remain in operation as long as
the voltage on H2 remains above 0.15 VDC.
NB. This control method cannot be used in conjunction with remote enable to
control the heat output of a heating circuit, as remote enable will turn off this
function. 0-10v only becomes active when the heating circuit(s) are in standby mode.
External / BMS controlled circulation pump essentials
When using a BMS or external control to operate the boiler, it is essential that the
pump circulating water around the boiler is interlocked with the demand for heat from
these controls, so that it should not be possible for the boiler to have a heating demand
without the circulation pump being in operation.
It is also essential that there is adequate provision of an over-run of the circulation
pump after the boiler has satisfied the heating demand, in order to prevent damage to
the heat exchanger. A minimum over-run time of 3 minutes is advised.
NB.
Even in standby mode, the built in frost protection program will activate when the
temperature detected inside the boiler drops below 5
O
C. This results in the boiler
switching on its burners, until the water temperature inside the boiler reaches 16
O
C, at
which point the burners switch off and the boiler returns to standby mode again. The
circulation pump MUST operate during this process.
Failure to provide adequate water circulation to the boiler, via operation of a
pump, when the gas burners are in operation may result in heat exchanger
damage and will invalidate the manufacturers warranty.
X1
X2
L
N
QX23
QX22
QX21
N
N
H2
M
BX21
BX22
U+
M
Module No
L
N
QX23
QX22
QX21
N
N
H2
M
BX21
BX22
U+
M
Module No
X1
X2
0-10 VDC Output
+
Siemens
Parameter
Parameter
description
Parameter
setting
Notes
6020
Function
extension
module
1
Multifunctional
H2
can
be
freely
configured
6046
Function
of
input
H2
module
1
Consumer
request
VK2
10V
0
‐
10V
signal
to
control
flow
temperature
setpoint
6047
Contact
type
H2
NO
or
NC
Not
relevant
to
this
function
6049
Voltage
valve
1
H2
0.5Vdc
Voltage
at
which
function
value
1
applies
6050
Function
value
1
H2
355
At
voltage
value
1
the
flow
temperature
setpoint
is
35.5
°
C
6051
Voltage
valve
2
H2
10.0Vdc
Voltage
at
which
function
value
2
applies
6052
Function
value
2
H2
820
At
voltage
value
2
the
flow
temperature
setpoint
is
82.0
°
C
Example
of
0
‐
10V
setup
using
expansion
module
1
Содержание SIRIUS FS
Страница 14: ...Sirius FS 12 GB IE 3 4 WIRING DIAGRAM PCB 1 ...
Страница 15: ...Sirius FS 13 GB IE 3 4 WIRING DIAGRAM PCB 2 ...
Страница 23: ...Sirius FS 21 GB IE 4 6 1 3 BASIC HEATING CIRCUIT HC1 HC2 DHW 4 6 1 4 BASIC HEATING CIRCUITS HC1 HC2 DHW SOLAR ...
Страница 45: ...Sirius FS 43 GB IE 6 5 3 Setting the Time and Date ...
Страница 64: ...Sirius FS 62 GB IE 7 5 COMPONENT ILLUSTRATIONS 25 2 37 36 35 23 24 23 24 38 39 28 28 33 33 38 39 44 42 43 ...
Страница 65: ...Sirius FS 63 GB IE 7 5 COMPONENT ILLUSTRATIONS CONTINUED 11 10 19 17 17 16 34 17 12 19 ...
Страница 66: ...Sirius FS 64 GB IE 7 5 COMPONENT ILLUSTRATIONS CONTINUED 30 29 8 13 18 5 1 3 4 32 21 15 14 7 9 20 6 ...
Страница 69: ...Sirius FS 67 GB IE 7 6 3 First Aid Kit Parts List continued 13 1 5 31 25 33 28 20 43 42 10 18 24 23 44 15 ...