Sirius FS
45
GB/IE
6.6.1 Lockout Display
The Display will show a if the boiler has locked out. More information can be obtained by
pressing the Info button on the HMI display screen. Example screen:
INFO
00:02
Error
30:Flow sensor 1
The number on the display indicates the number of the PCB that the fault has occurred on
In this example a flow sensor error has occurred on the second burner (PCB 2).
6.6.2 E
ngineering Mode - further fault detail
To enter Engineer Mode:
- Press OK then hold down the Info button for more than 3 seconds.
- Select Engineer from the list using the Wheel, then press OK.
- Use the Wheel to scroll down to ‘Fault’ and press OK.
- Step through the lines 6800 to 6995 to list the last 20 faults. The first screen gives the
general fault and the time and date of its occurrence. Example screen:
Prog
No
6800
09:32
26.01.2012
Fault
History 1
133: Safety Time Exceeded
Page two of fault history records specific details about what the software and controls were
indicating at the precise moment the fault occurred. Example screen:
Prog
No
6805
625
Fault
SW diagnostic code 1
Burner control phase 1 3
A complete listing of displayed fault codes is given in the Operating and
Programming guide.
Содержание SIRIUS FS
Страница 14: ...Sirius FS 12 GB IE 3 4 WIRING DIAGRAM PCB 1 ...
Страница 15: ...Sirius FS 13 GB IE 3 4 WIRING DIAGRAM PCB 2 ...
Страница 23: ...Sirius FS 21 GB IE 4 6 1 3 BASIC HEATING CIRCUIT HC1 HC2 DHW 4 6 1 4 BASIC HEATING CIRCUITS HC1 HC2 DHW SOLAR ...
Страница 45: ...Sirius FS 43 GB IE 6 5 3 Setting the Time and Date ...
Страница 64: ...Sirius FS 62 GB IE 7 5 COMPONENT ILLUSTRATIONS 25 2 37 36 35 23 24 23 24 38 39 28 28 33 33 38 39 44 42 43 ...
Страница 65: ...Sirius FS 63 GB IE 7 5 COMPONENT ILLUSTRATIONS CONTINUED 11 10 19 17 17 16 34 17 12 19 ...
Страница 66: ...Sirius FS 64 GB IE 7 5 COMPONENT ILLUSTRATIONS CONTINUED 30 29 8 13 18 5 1 3 4 32 21 15 14 7 9 20 6 ...
Страница 69: ...Sirius FS 67 GB IE 7 6 3 First Aid Kit Parts List continued 13 1 5 31 25 33 28 20 43 42 10 18 24 23 44 15 ...