8.2.4
User settings (optional)
8.2.4.1
Define standard measuring unit for flow rate
Uni
Select and define measuring unit.
Lmin
= Flow rate in standard litre / minute
nm3h
= Flow rate in standard cubic metre / hour
nmS
= Flow velocity in standard metre / second.
The setting has only an effect on the flow rate value.
Set the display unit before setting the values for the parameters
SPx,
rPx, ASP
and
AEP.
By this, rounding errors are avoided during the
internal conversion to other units and the desired values are exactly
obtained.
8.2.4.2 Configure standard display
SELd
Select and define standard measuring unit.
FLOW
= Display shows current flow rate value in
standard measuring unit
TOTL
= Display shows current counter reading in Nm³ or 1000 Nm³
TEMP
= Display shows current media temperature in °C
diS
Select and define updating rate and orientation of the display.
d1
= Measured value updating every 50 ms
d2
= Measured value updating every 200 ms
d3
= Measured value updating every 600 ms
rd1
,
rd2
,
rd3
= Display as d1, d2, d3; rotated by 180 °
OFF
= The display is switched off in the working mode,
on pressing the button, the process value appears for 15 s.
8.2.4.3
Set measured value damping
dAP
Select and set damping constant in seconds
(t-value 63%).
8 Progr Parameter setting