www.poolpak.com | 800-959-7725
62
| ComPak
®
Series - Installation, Operation and Maintenance
• Bypass Solenoid Status
• Compressor Status
• Reheat Solenoid Status
TIME AND DATE
The time and date that the alarm occurred will show for each alarm instance. To configure time and date,
see Service>Utilities.
Manual Mode
The Manual Mode menu provides two options, Demand Control and Digital Output Control.
DEMAND CONTROL
• Enabled: Yes or No. This parameter enables manual demand mode. In this mode, the routines that normally
control air temperature, humidity, and pool temperature are bypassed. A service technician can then enable
individual demands to test each system in the dehumidifier.
• Cmpr Air Heat: Off or On. Set to On to cause the unit to run the compressor in air heating mode.
• Air Cooling: Off or On. Set to On to cause the unit to run the compressor in air cooling mode.
• Pool Heating: Off or On. Set to On to cause the unit to enable compressor based pool water heating. This
will not cause the compressor to run. The compressor must be running based on one of the other demands.
• Aux Air Heat 1: Off or On. Set to On to activate the first stage of auxiliary air heat.
• Aux Air Heat 2: Off or On. Set to On to activate the second stage of auxiliary air heat.
• Aux Water Heat: Off or On. Set to On to activate the auxiliary pool water heating system.
• Economizer: Off or On. Set to On to activate the field provided and installed economizer damper system.
DIGITAL OUTPUT CONTROL
• Fan Motor: Auto, On, or Off. Set to On or Off to force the dehumidifier fan on or off.
• Compressor: Auto, On, or Off. Set to On or Off to force the dehumidifier compressor on or off. Do not force
compressor operation unless the appropriate solenoid valves are open. Doing so will cause the compressor
to cycle repeatedly on the high pressure cutout. This will destroy the compressor.
• AC Valve: Auto, On, or Off. Set to On or Off to force the AC solenoid valve open or closed.
• Water Ht Vlv: Auto, On, or Off. Set to On or Off to force the pool heating solenoid valve open or closed.
• Bypass Valve: Auto, On, or Off. Set to On or Off to force the bypass solenoid valve open or closed.
• Aux Water Heat: Auto, On, or Off. Set to On or Off to force the auxiliary pool heating system on or off.
• Reheat Valve: Auto, On, or Off. Set to On or Off to force the reheat solenoid valve open or closed.
• Aux Air Ht 1: Auto, On, or Off. Set to On or Off to force auxiliary air heating system stage 1 on or off.
• Aux Air Ht 2: Auto, On, or Off. Set to On or Off to force auxiliary air heating system stage 2 on or off.
• ACC Fan: Auto, On, or Off. Set to On or Off to force the ACC run signal on or off.
• Alarm Output: Auto, On, or Off. Set to On or Off to force the alarm output contacts closed or open.
• Economizer: Auto, On, or Off. Set to On or Off to force the field provided and installed economizer damper
system to full open or full close.
Manual mode operation should only be performed by a qualified HVAC service technician.
Improper use will cause system damage and possibly hazardous operation.
!
WARNING!