© 2017 PoolPak LLC. All rights reserved.
ComPak
®
Series - Installation, Operation and Maintenance |
49
ComPak
®
Series IOM
Status Screen 2 displays:
• Water Heating - YES or NO
• YES indicates that the unit is returning recovered heat back to the pool water.
• Aux Water Heat - YES or NO
• YES indicates that the controller has closed the relay contact requesting auxiliary pool water heater
operation.
• Water Temperature in °F or °C
Status Screen 3 displays:
• SPACE temperature control requirement:
• TEMPERATURE- OK Indicates the space temperature is at setpoint.
• HEATING- YES Indicates the space requires heating.
• COOLING- YES Indicates the space requires cooling.
• AUX AIR HEAT- YES or NO Indicates the space requires additional heating. The auxiliary air heating relay
contacts close to activate the external heating system.
• DEHUMID (SURFACE) - YES or NO Indicates the space requires dehumidification. The word SURFACE
indicates that the unit is temporarily lowering the dew point set point to minimize condensation at the cold
surface temperature sensor.
• ECONOMIZER MODE- YES or NO Indicates the unit is cooling the space with outside air. ECONOMIZER
MODE is only shown if the optional economizer system is present.
Figure 5-4 Status Screen 4
Status Screen 4 displays the current system status as follows:
• Line 1: Day, Date and Time
• Line 2: Pool water flow status for units configured as full pool water heating. Possible text values include:
• Water Flow Normal
• Water Flow Too Low
• Line 3: Text relating the current active fault code. Possible text values include:
• All systems normal
• Unit is in OFF mode
• Sys Startup Active
• Fan Motor Overload
• Fire Trip Active
• Abnormal Space Temp
• Defrost Switch Open
• Cmpr Low Pressure
• Cmpr High Mtr Temp
• Cmpr High Pressure
• Space T Sens Fail
• Space RH Sens Fail Pool T Sens Fail
• Outs T Sens Fail