ComPak
®
Series - Installation, Operation and Maintenance |
63
ComPak
®
Series IOM
Utilities
The Utilities menu provides sub menus for configuring units of measure, passwords and time and date.
UNITS OF MEASURE
• Temperature Units: ˚F or ˚C. When set to ˚C, commonly used parameters and set points will be shown in
degrees Celsius. Some configuration parameters are shown in ˚F only.
PASSWORDS
• Set Point: 0000 (Range 0000 to 9999). When set to a non-zero value, this parameter causes the RIU to
prompt for a password when any of the set point change menus are accessed. The required password is the
value of this parameter.
• Service: 0005 (Range 0000 to 9999). This is the password required to access most service menus.
• Advanced Password (not shown): 9995. This is the password required for access to service sub-menus.
SET TIME AND DATE
• Time: set this to the current time as 24-hour time clock, HH:MM:SS. For example, for 1:24:00, use 13:24:00
• Day of Week: set this to the current day of the week.
• Date: set this to the current date, MM/DD/YY
Startup
Pre-Start Checklist
• Before starting the unit, be sure that the following items have been completed.
• Check that the unit physical installation (ducting, piping, etc.) is in accordance with the recommendations of
the Installation section.
• Verify electrical power and control connections are in accordance with local and NEC codes. Check for
proper power supply and a properly sized and installed fused disconnect switch located within sight of the
ComPak® unit.
• Ensure that proper pool water flow and pressure are available. Check the water flow direction into and out
of the unit. Make sure that the ComPak® unit is down line from the filter and up line from the chemical feed
system.
• Check that the condensate drain is connected. If returning condensate to the pool, ensure that this practice is
in compliance with local codes. Make sure that the condensate is filtered prior to returning to the pool.
• Check that the overflow drain (AWV and HCDV only) is connected independent of the condensate drain. If
returning the overflow to the pool, ensure that this practice is in compliance with local codes. Make sure that
the overflow is filtered prior to returning to the pool.
• Ensure that the space air temperature of the pool enclosure is not lower than 72°F, and the temperature of the
pool water is at least 70°F.
• If the ComPak® unit is equipped with the auxiliary air-cooled air conditioning condenser, ensure that it has
been correctly wired and piped and that the control wiring has been connected between the ComPak® and
the ACC unit. See “Air Cooled Condenser Installation,” for installation recommendations.
• If the ComPak® unit is equipped with the auxiliary water-cooled air conditioning condenser, ensure that
proper water flow and temperature are available. Check the water flow direction into and out of the unit.
Figure 5-15. Time and Date Screen