www.poolpak.com | 800-959-7725
26
| ComPak
®
Series - Installation, Operation and Maintenance
Remote Air-Cooled Condenser (ACC) Performance
Table 3-8. Remote ACC Performance Chart
Note: Below table contains the piping sizes of the remote ACC stub-outs. Additional field piping may be
needed to make the transition from the connections to correct refrigeration lineset sizing (See
Table 4-3
.)
UNIT
SIZE
ACC
MODEL*
AMBIENT TEMP
(°F)
UNIT
HEIGHT
(INCHES)
VAPOR
O.D.
(INCHES)
LIQUID
O.D.
(INCHES) UNIT
WEIGHT
MOTOR FLA
MIN. CIRCUIT
AMPACITY
A
B
C
208/230V 460V 208/230V 460V
0550
ACC0041
95/100/105/115
39.3
5/8
1/2
120
3
1.5
3.8
1.9
0800
ACC0041
95/100/105
39.3
5/8
1/2
120
3
1.5
3.8
1.9
ACC0051
110
3/4
1/2
120
ACC0081
115
7/8
5/8
210
1200
ACC0051
95/100/105
39.3
3/4
1/2
120
3
1.5
3.8
1.9
ACC0081
110
7/8
5/8
210
ACC0121
115
39.3
1-1/8
3/4
470
6
3
7.5
3.8
1400/1800
ACC0081
95/100/105
39.3
7/8
5/8
210
3
1.5
3.8
1.9
ACC0121
110/115
39.3
1-1/8
3/4
470
6
3
7.5
3.8
2600
ACC0121
95/100/105/110
39.3
1-1/8
3/4
470
6
3
7.5
3.8
ACC0301
115
49.0
1-1/8
7/8
640
14
7
20
15
3500
ACC0161
95/100/105
39.3
1-1/8
7/8
470
6
3
7.5
3.8
ACC0301
110
49.0
640
14
7
20
15
ACC0341
115
690
4000
ACC0161
95/100
39.3
1-1/8
7/8
470
6
3
7.5
3.8
ACC0211
105
40.5
550
10
5
11.2
5.6
ACC0301
110
49.0
640
14
7
20
15
ACC0341
115
690
*NOTES: For models ACC00XX, see figure #3-3 (Single Fan).
For models ACC01XX, see figure #3-3 (Dual Fan).
For models ACC02XX, see figure #3-4 (Three Fan-Bohn).