Preparing Your Room for the Polycom Open Telepresence Experience (OTX) 300 Installation
Page 16 of 32
Power and Cooling
The following table lists the power and cooling requirements:
Power and Cooling
Total Power
(Watts)
BTUs/Hour
Cooling in Tons
With OTX in Standby
(All components off except for rack
components and cameras)
300
1025
.09
With OTX in Use
(Using maximum call rate and content
sharing)
2000
6824
.57
For Complete Experience Kit Lighting
810
2764
.23
Maximum
2500
8530
.71
Note that this table includes only the OTX components and not the participants, laptops, and lighting.
Thermostat
Polycom recommends installing an independently controlled thermostat on a side wall in the room.
The operating temperature for the OTX equipment should be within 41° to 86° F (5° to 30° C).
Obstructions
As shown on pages 23 and 24, the room in which the OTX will be installed must be clear of any
architectural elements that would restrict access, lessen usable space, or prevent people from easily
and safely walking around the room. Examples include room columns and soffits on the walls or
ceiling.