Automist Smartscan Hydra
®
DIOM Manual - version 3.01.0
Plumis Ltd Copyright © 2020. All Rights Reserved.
Page 99 of 116
S MA RT SC AN
®
IMPORTANT!
The flasher may turn off after a while. Simply press the power button to turn back on.
Programming
Press the 6pin needle adapter into the controller PCB programming port. The four support legs may need
to be pinched in as you press the adapter into the PCB. When fully inserted the needle adapter will be
locked to the PCB.
We are now ready to update the controller software. If necessary, turn the flasher on, then press the 'PROG'
button on the Flasher. Watch the Flasher display, it will say "Erasing", then "Programming", and finally "OK".
Note: If the red "ERROR" is displayed, please check your connection, and retry. If it persists, contact Plumis
R&D for advice. Note: The Hydra heads will lock and start flashing red x4. The heads will remain like this
until we reset the controller in the next section.
Figure 90: Updating the software