![Plumis Automist Smartscan Hydra Скачать руководство пользователя страница 74](http://html1.mh-extra.com/html/plumis/automist-smartscan-hydra/automist-smartscan-hydra_design-installation-operation-and-maintenance-diom-manual_1568686074.webp)
Automist Smartscan Hydra
®
DIOM Manual - version 3.01.0
Plumis Ltd Copyright © 2020. All Rights Reserved.
Page 74 of 116
S MA RT SC AN
®
vii.
Hose
v.
Washer
4.
Pump
Figure 68: Automist Smartscan Hydra Water Assembly Order
IMPORTANT!
Do not install the filter directly to the pump. You must maintain the assembly order as
described above!
The new hose-sets supplied with the appliance are to be used and the old hose-sets must
not be reused. To enable a consistent pressure and seal for all low-pressure water interface washers, the
correct amount of torque must be applied to each low-pressure connection. This can be accomplished in
two ways (with the washers and mating surfaces kept dry):
i)
Apply 6Nm using a calibrated torque wrench
OR
ii)
Hand tighten the hose. Using a conventional wrench, apply another 1/2 turn clockwise to
guarantee a reliable seal.
IMPORTANT!
Switch on the water supply. Check and verify that there is no leak at any component between
the main water supply port and pump inlet port when the water supply is switched on. Switch on and off
any water tap nearby several times to simulate water hammer effect and verify that there is no leak at any
component.
i
ii
iii
iv
v
vi
v
vii
v