S MA RT SC AN
®
covered by servo motor shaft). Check all sprayheads during each flow test or draining step. Dry
the parts if water is visible.
Figure 76: Commissioning mode – commissioning flow state
The sprayheads will glow red and lock pending head selection. Press the first sprayhead and
initiate a scan test. The head will scan once and point to the warmest position that it observes
which must be your hand. It will then rest in an approximately 90-degree position and turn
solid yellow if the scan test was successful.
If unsuccessful, the head will remain solid red and
return to the locked position. Gently push the head to retry the scan test. If it still fails, turn off
the system, and visibly check the sensor is clean of any dust or water. The sensor must see a
temperature difference during the scan for the test to pass.
Figure 77: Testing the IR sensor and selecting the head for flow testing
Unscrew the cap on the quick connect test point (see page 73) and connect the test hose and
gauge to the test point adapter. Connect the commissioning kit to the selected sprayhead and
place a bucket on the floor to collect the water. Ensure the volume of water reaches the
approximate 6lt level mark in the bucket.
GREEN LED flashing
three times, YELLOW
LED flashing the
number of flow
tested heads