![Plumis Automist Smartscan Hydra Скачать руководство пользователя страница 49](http://html1.mh-extra.com/html/plumis/automist-smartscan-hydra/automist-smartscan-hydra_design-installation-operation-and-maintenance-diom-manual_1568686049.webp)
Automist Smartscan Hydra
®
DIOM Manual - version 3.01.0
Plumis Ltd Copyright © 2020. All Rights Reserved.
Page 49 of 116
S MA RT SC AN
®
C-Tec
•
Multi-Sensor Fire Detector (kitchen only)
https://www.c-tec.com/activ-fire-detectors/c4414-activ-multi-sensor-fire-detector.html
•
Optical Smoke Detector
https://www.c-tec.com/activ-fire-detectors/c4414-activ-multi-sensor-fire-detector.html
The following fire panels are compatible with the Automist system, because they monitor the detector
status and have a battery backup in case of power loss:
•
CFP Economy 2-4-8 Zone Conventional Fire Alarm Panel
https://www.c-tec.com/conventional-fire-systems/cfp-2-8-zone-fire-panels/
•
Hush Pro
Hush-Pro by C-TEC provides fully monitored BS 5839-6 Grade C compliant fire detection, alarm,
silencing and test facilities in domestic dwellings such as flats and apartments. As well as putting
residents firmly in control of their own fire systems by allowing them to test and silence devices
whilst standing at floor level, multiple Hush-Pro systems can be interfaced to a landlord system in a
tall building to help make stay-put safer.
Plumis Wireless Smoke Heat Alarm (DT01)
The Wireless Smoke Heat Alarm is a 3xAAA battery powered wireless alarm custom designed for use with
an Automist Smartscan Hydra sprayhead only. The alarm has a built-in wireless transmitter, which
communicates with the control panel via the sprayhead receivers. When smoke is detected, the alarm
sounds a loud local alarm, and the built-in transmitter sends a signal to the control panel. The Wireless
Smoke Heat Alarm contains an integrated fixed 5°C temperature freeze sensor that will send a warning
signal based on temperature detected. This alarm is designed to provide protection with 21 meters spacing
capability. The detector can send alarm, tamper, and battery condition messages to the Automist
Smartscan Hydra’s controller. Refer to the wireless alarm instructions for more details.
Content
•
Wireless Smoke Heat Alarm with base
•
Pack of screws and anchors
•
Labels or decals as appropriate
•
3 AAA PC2400 Duracell Procell batteries (1.5V 1100mAh), or
3 AAA Energizer E92 batteries (1.5V 1100mAh)
The Wireless Smoke Heat Alarm contains a sounder which generates the ANSI S3.41 temporal 3 pattern in
an alarm condition. In alarm, a message is also sent to the control panel. Installation of the mounting base
is simplified by the incorporation of features compatible for both drywall fasteners (not supplied) and other
methods.
Specification
•
Operating Frequency: 2.4 GHz
•
Maximum Transmit Power: 10 dBm
•
Protocol: Plumis proprietary
•
Detector fault detection, tamper detection, dirty detector, freeze warning, battery low warning
•
Compliant to EU Radio Equipment Directive (EN ETSI 300 328, EN ETSI 301 489-17, EN50131-4)