Automist Smartscan Hydra
®
DIOM Manual - version 3.01.0
Plumis Ltd Copyright © 2020. All Rights Reserved.
Page 66 of 116
S MA RT SC AN
®
.
Figure 59: Connecting the controller
Connect the wiring to the terminals as per the drawing (see page 60). Use a torque screwdriver on the
following setting: minimum 0.22Nm, maximum 0.25Nm. (Note: the green connector block has Phoenix
Contact MKDS 1/5-3,5).
Required tools:
•
Torque Screwdriver: Duratool DT000230 (CPC)
•
Screwdriver Set: Tacklife HPSB1A 58-in-1 precision screwdriver bits (Amazon)
Reconnect the ribbon to the pin header connector. Place the control unit enclosure lid over the base and fix
the lid.
C) Second Fix - Installing the sprayhead(s) and pump
Place the
first sprayhead
loosely in the mounting hole and connect the data cable between the terminals
on the pump to the incoming terminals on the sprayhead.
Tighten the wires of the Smartscan Hydra Head Cable into the screw terminals. Use a torque screwdriver on
the following setting: minimum 0.22Nm, maximum 0.25Nm (Note: the green connector block has Phoenix
Contact MKDS 1/5-3,5).
Hydra connections use ‘Rising Clamp’ type of terminal. It is
very important
to operate the terminals
correctly, otherwise they will not make reliable electrical connection and won’t properly clamp the wire.
Wall mounting
screw holes
Lid screw
Gland for electrical
connections
Ribbon to front
enclosure panel
Pin header
Connector