Automist Smartscan Hydra
®
DIOM Manual - version 3.01.0
Plumis Ltd Copyright © 2020. All Rights Reserved.
Page 113 of 116
S MA RT SC AN
®
Example Design Specification
a)
Building/occupancy type
Three story loft conversion/single dwelling
b)
Areas of the building to be protected
Throughout, except for the following areas, which may be excluded unless required by a fire
strategy or risk assessment:
•
bathrooms fitted with a door and with a floor area of less than 5 m
2
;
•
cupboards and pantries fitted with doors and with a floor area of less than 2 m
2
, and
rooms in which the smallest dimension does not exceed 1 m, where the walls and ceilings
are covered with non-combustible or limited-combustible materials;
•
non-communicating, attached buildings such as garages, boiler houses, etc.;
See layout drawing
c)
Water supply requirements and verification measures
Minimum flow and pressure recorded on each pump at peak demand: 8 lpm and 2 bar pressure
d)
How Automist interacts with fire alarm system
Completely stand alone. Automist’s detection is installed alongside a pre-existing LD1 system.
e)
Details of any enhancements to Automist
Not applicable
f)
Where a fire strategy relies upon the design of the automatic water fire suppression system
(AWFSS), a version-controlled copy of that fire strategy, including sufficient detail to
understand the fire safety objectives, relationships, and dependencies
See BS 9991 Section 6.5 (see 11.2, Table 2)
h)
Any deviations from the DIOM
None