The gas linkage attached to the device allows to place the gas cylinder maximally 3 metres away from the connected
control panel, however it cannot be placed nearer to the device than 1,5 metres.
Fig. 7
–
Location of gas cylinder
•
The optional housing for the gas cylinder cannot be airtight and has to be correctly ventilated. The housing needs
to have an upper ventilation slot above the top of the bottle (of an area min 1/100 of the area of the base of the
housing) and a lower ventilation slot (of an area min 1/50 of the area of the base of the housing). The dimensions
of the housing may vary to accommodate different types and dimensions of the gas cylinders however they also
have to be sufficient for hassle-free installation of the gas cylinder.
Fig. 8
–
Housing for gas cylinder
o
After making sure that
the device has been correctly installed acquaint yourself with the attached User’s Manual.
o
Only after acquainting yourself with the User’s Manual and correctly attaching the gas linkage may you start the
device.
o
If in future a need arises of having to take the insert out of the housing it may only be done when the device is
turned off and cooled down and the valve on the gas cylinder is closed.
o
Keep this instruction manual for the lifetime of the device.